SITRANS FM100
A5E48762204-AA page 61
Index
[hex]
Name
Description
Factory default
Max Value
Min Value
Length
[Bytes]
Data Type
Access
0x0147
OUT1Frequencyat
FS
Max. frequency in
Hz for the output
500
1000
50
2
UIntegerT
R/W
0x0149
OUT1Frequency
Overflow
Overflow
frequency in
percent of the max
frequency
1
100
0
1
UIntegerT
R/W
0x014A
OUT1Frequency
Value0Hz
Value from source
used for 0 Hz
scaling point
0,0
OUT1
Frequency
ValueMaxHz
MRS
4
FloatT
R/W
0x014E
OUT1Frequency
ValueMaxHz
Value from source
used for max. Hz
scaling point
100,0
MRE
OUT1
Frequency
Value0Hz
4
FloatT
R/W
0x0152
OUT1CtrlFunction
Controlinput-
function -> Off or
Memoryreset
0
(0) - Off
(1) - Memoryreset
1
UIntegerT
R/W
Output 2
0x0163
OUT2Source
Source for the
output
0
(0) - Flow
(1) - Volume
(2) - Temperature
(3) - Part Volume
1
UIntegerT
R/W
0x0164
OUT2Type
Configuration of
the output ->
0-20mA, Pulse,
Frequency, etc.
0
(0) - disabled
(1) - Alarm Output
(2) - 4-20mA
(3) - 0-20mA
(4) - 2-10V
(5) - 0-10V
(6) - Pulse Output
(7) - Frequency Output
1
UIntegerT
R/W
0x0165
OUT2Alarm
Function
Limit or window
function for the
alarm output
0
(0) - Limit
(1) - Window
1
UIntegerT
R/W
0x0166
OUT2AlarmOutput
Type
Alarmoutput NPN,
PNP or Pushpull
0
(0) - NPN
(1) - PNP
(2) - PushPull
1
UIntegerT
R/W
0x0167
OUT2AlarmSwitch
Function
Alarmoutput
normally opened
or closed
0
(0) - normally opened
(1) - normally closed
1
UIntegerT
R/W
0x0168
OUT2Alarm
Threshold
Threshold for the
alarmoutput
1,0
MRE
MRS
4
FloatT
R/W
0x016C
OUT2AlarmLower
Threshold
Threshold for the
alarmoutput used
by the
windowfunction
1,0
OUT2AlarmT
hreshold
MRS
4
FloatT
R/W