EasyManua.ls Logo

Siemens SITRANS F US - Profile 18

Siemens SITRANS F US
194 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix A
A.1 Modbus, EIP, HART & N2 Profile Mappings
F US Clamp-on Communications Protocol Manual
Hardware Installation Manual, 11/2015, A5E34981613-AC
101
A.1.19
Profile 18
Profile 18 (FUS1010-5MN01-5.04.05-1+2+3+4CO)
Data Description
Modbus
Ethernet/IP
HART
N2
Reg
Bytes
Type
Tag Name
OS
Format
CMD
VAR
Type
Ad
Sz
Site ID
30501
8
String
String_In
0
UINT16
n/a
BD(Byte)
1
8
Date: Year
30101
2
Integer
Analog_In
0
Float
n/a
ADI(Int)
1
1
Date: Month
30102
2
Integer
Analog_In
1
Float
n/a
ADI(Int)
2
1
Date: Day
30103
2
Integer
Analog_In
2
Float
n/a
ADI(Int)
3
1
Time: Hour
30104
2
Integer
Analog_In
3
Float
n/a
ADI(Int)
4
1
Time: Minute
30105
2
Integer
Analog_In
4
Float
n/a
ADI(Int)
5
1
Time: Second
30106
2
Integer
Analog_In
5
Float
n/a
ADI(Int)
6
1
C1 Inst.Flow
Rate
30109 4 Real Analog_In 6 Float 129 6-06h T ADF(Float) 1 1
C1 Flow Rate
Units
30517 8 String String_In 4 UINT16 131 6-06h BD(Byte) 9 8
C2 Inst.Flow
Rate
30111 4 Real Analog_In 7 Float 129 7-07h Q ADF(Float) 2 1
C2 Flow Rate
Units
30521 8 String String_In 8 UINT16 131 7-07h BD(Byte) 17 8
C3 Inst.Flow
Rate
30113 4 Real Analog_In 8 Float 129 8-08h ADF(Float) 3 1
C3 Flow Rate
Units
30525 8 String String_In 12 UINT16 131 8-08h BD(Byte) 25 8
C4 Inst.Flow
Rate
30115 4 Real Analog_In 9 Float 129 9-09h ADF(Float) 4 1
C4 Flow Rate
Units
30529 8 String String_In 16 UINT16 131 9-09h BD(Byte) 33 8
C5 Inst.Flow
Rate
30117 4 Real Analog_In 10 Float n/a ADF(Float) 5 1
C5 Avg Flow
Rate
30129 4 Real Analog_In 11 Float 129 5-05h P ADF(Float) 6 1
C5 Flow Rate
Units
30533 8 String String_In 20 UINT16 131 5-05h BD(Byte) 41 8
C1 Total
30145
4
Real
Analog_In
12
Float
129
34-22h
ADF(Float)
7
1
C1 Total Units 30557 8 String String_In 24 UINT16 131 34-22h BD(Byte) 49 8
C2 Total
30147
4
Real
Analog_In
13
Float
129
35-23h
ADF(Float)
8
1
C2 Total Units
30561
8
String
String_In
28
UINT16
131
35-23h
BD(Byte)
57
8
C3 Total
30149
4
Real
Analog_In
14
Float
129
36-24h
ADF(Float)
9
1
C3 Total Units
30565
8
String
String_In
32
UINT16
131
36-24h
BD(Byte)
65
8
C4 Total
30151
4
Real
Analog_In
15
Float
129
37-25h
ADF(Float)
10
1
C4 Total Units
30569
8
String
String_In
36
UINT16
131
37-25h
BD(Byte)
73
8
C5 Total
30153
4
Real
Analog_In
16
Float
129
38-26h S
ADF(Float)
11
1
C5 Total Units
30573
8
String
String_In
40
UINT16
131
38-26h
BD(Byte)
81
8
C1 Sonic Vel
30157
4
Real
Analog_In
17
Float
n/a
ADF(Float)
12
1
C2 Sonic Vel
30159
4
Real
Analog_In
18
Float
n/a
ADF(Float)
13
1
C3 Sonic Vel
30161
4
Real
Analog_In
19
Float
n/a
ADF(Float)
14
1
C4 Sonic Vel
30163
4
Real
Analog_In
20
Float
n/a
ADF(Float)
15
1
Sonic Vel Units
30577
8
String
String_In
44
UINT16
n/a
BD(Byte)
89
8

Table of Contents