Appendix A
A.1 Modbus, EIP, HART & N2 Profile Mappings
F US Clamp-on Communications Protocol Manual
Hardware Installation Manual, 11/2015, A5E34981613-AC
97
Temp Units
30753
8
String
String_In
32
UINT16
n/a
BD(Byte)
65
8
Aux Input 1
30285
4
Real
Analog_In
17
Float
n/a
ADF(Float)
12
1
Aux 1 Type
30813
8
String
String_In
36
UINT16
n/a
BD(Byte)
73
8
Aux Input 2
30287
4
Real
Analog_In
18
Float
n/a
ADF(Float)
13
1
Aux 2 Type
30817
8
String
String_In
40
UINT16
n/a
BD(Byte)
81
8
A.1.18
Profile 17
Profile 17 (FUS1010-5MN01-5.04.05-1CO2CO3CO4CO)
Data Description
Modbus
Ethernet/IP
HART
N2
Reg
Bytes
Type
Tag Name
OS
Format
CMD
VAR
Type
Ad
Sz
C1 Site ID
30501
8
String
String_In
0
UINT16
n/a
BD(Byte)
1
1
Date: Year
30101
2
Integer
Analog_In
0
Float
n/a
ADI(Int)
1
1
Date: Month
30102
2
Integer
Analog_In
1
Float
n/a
ADI(Int)
2
1
Date: Day
30103
2
Integer
Analog_In
2
Float
n/a
ADI(Int)
3
1
Time: Hour 30104 2 Integer Analog_In 3 Float n/a ADI(Int) 4 1
Time: Minute
30105
2
Integer
Analog_In
4
Float
n/a
ADI(Int)
5
1
Time: Second 30106 2 Integer Analog_In 5 Float n/a ADI(Int) 6 1
C1 Inst.Flow
Rate
30109 4 Real Analog_In 6 Float 129 6-06h ADF(Float) 1 1
C1 Avg Flow
Rate
30121 4 Real Analog_In 7 Float 129 1-01h P ADF(Float) 2 1
C1 Flow Rate
Units
30517 8 String String_In 4 UINT16 131 1-01h BD(Byte) 9 8
C1 Raw Flow
30133
4
Real
Analog_In
8
Float
n/a
ADF(Float)
3
1
C1 Raw Flow
Units
30537 8 String String_In 8 UINT16 n/a BD(Byte) 17 8
C1 Total
30145
4
Real
Analog_In
9
Float
129
34-22h
ADF(Float)
4
1
C1 Total Units
30557
8
String
String_In
12
UINT16
131
34-22h
BD(Byte)
25
8
C1 Sonic Vel
30157
4
Real
Analog_In
10
Float
n/a
ADF(Float)
5
1
C1 Sonic Vel
Units
30577 8 String String_In 16 UINT16 n/a BD(Byte) 33 8
C1 Signal
Strength
30167 2 Integer Analog_In 11 Float n/a ADF(Float) 6 1
C1 Sig Strength
Units
30593 8 String String_In 20 UINT16 n/a BD(Byte) 41 8
C1 Aeration
30172
2
Integer
Analog_In
12
Float
n/a
ADF(Float)
7
1
C1 Aeration Units
30609
8
String
String_In
24
UINT16
n/a
BD(Byte)
49
8
C1 Status
/Alarms: Spacing
10021 1 Bit Coil Binary_In 0 UINT16 n/a DI(Dig In) 1 1
C1 Status
/Alarms: Empty
10022 1 Bit Coil Binary_In 0 UINT16 n/a DI(Dig In) 3 1
C1 Status
/Alarms: Rate
10023 1 Bit Coil Binary_In 0 UINT16 n/a DI(Dig In) 4 1
C1 Status
/Alarms: Fault
10024 1 Bit Coil Binary_In 0 UINT16 n/a DI(Dig In) 5 1