EasyManua.ls Logo

Siemens SITRANS F US - Device functions and parameters; 6.1 Main menu: Display (menu 1)

Siemens SITRANS F US
194 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
BACnet Communications
3.2 BACnet Protocol Implementation Conformance Statement
F US Clamp-on Communications Protocol Manual
Hardware Installation Manual, 11/2015, A5E34981613-AC
31
Binary Input Object
Property Identifier
Description and/or Example Value
Object_Identifier
Unique Identifier (e.g. 20971525)
R
Object_Name
(see list of Binary Input objects)
(e.g. C1_Pipe_Empty)
R
Object_Type
3 Binary Input
R
Present_Value
R
Description
Character String (e.g. C1_Pipe_Empty)
R
Status_Flags IN_ALARM,FAULT,OVERRIDDEN,OUT_OF_SERVICE
(e.g. 0000)
R
Event_State
0 - Normal
R
Out_Of_Service
0 - False
R
Reliability
0
R
Active Text
Active
R
Inactive Text Inactive R
3.2
BACnet Protocol Implementation Conformance Statement
A BACnet Conformance Statement is included with each communications module. It is a
reference for the installer that lists the applicable specifications for each individual BACnet
communications setup.
Typical BACnet Conformance Statement
Date:
January, 2012
Vendor Name:
Siemens Industry, Inc.
Product Name:
SITRANS F US Clamp
-On Ultrasonic
Flowmeters
Product Model Number:
Siemens Option Card
Application Software Version:
V6.11b (A)
Firmware Revision:
2.04.06
BACnet Protocol Revision:
1
Product Description:
Clamp-on ultrasonic flowmeter
BACnet Standardized Device Profile (Annex L):
BACnet Operator Workstation (B-OWS)
BACnet Advanced Operator Workstation (B-
AWS)
BACnet Operator Display (B-OD)
BACnet Building Controller (B-BC)
BACnet Advanced Application Controller (B-
AAC)
BACnet Application Specific Controller (B-ASC)
BACnet Smart Sensor (B-SS)
BACnet Smart Actuator (B-SA)
List all BACnet Interoperability Building Blocks Supported (Annex K):

Table of Contents

Other manuals for Siemens SITRANS F US

Related product manuals