Appendix A
A.1 Modbus, EIP, HART & N2 Profile Mappings
F US Clamp-on Communications Protocol Manual
Hardware Installation Manual, 11/2015, A5E34981613-AC
119
A.1.24
Profile 23
Profile 23 (FUE1010-5EN02-5.04.05-1CO)
Data Description
Modbus
Ethernet/IP
HART
N2
Reg
Bytes
Type
Tag Name
OS
Format
CMD
VAR
Type
Ad
Sz
Site ID
30501
8
String
String_In
0
UINT16
n/a
BD(Byte)
1
1
Date: Year
30101
2
Integer
Analog_In
0
Float
n/a
ADI(Int)
1
1
Date: Month
30102
2
Integer
Analog_In
1
Float
n/a
ADI(Int)
2
1
Date: Day
30103
2
Integer
Analog_In
2
Float
n/a
ADI(Int)
3
1
Time: Hour
30104
2
Integer
Analog_In
3
Float
n/a
ADI(Int)
4
1
Time: Minute
30105
2
Integer
Analog_In
4
Float
n/a
ADI(Int)
5
1
Time: Second
30106
2
Integer
Analog_In
5
Float
n/a
ADI(Int)
6
1
Avg Energy Rate
30199
4
Real
Analog_In
6
Float
129
39-27h T
ADF(Float)
1
1
Inst.Energy Rate 30193 4 Real Analog_In 7 Float n/a ADF(Float) 2 1
Energy Rate Units
30653
8
String
String_In
4
UINT16
131
39-27h
BD(Byte)
9
8
Energy Total
30205
4
Real
Analog_In
8
Float
129
42-2Ah Q
ADF(Float)
3
1
EnergyTotal Units
30661
8
String
String_In
8
UINT16
131
42-2Ah
BD(Byte)
17
8
Inst.Flow Rate
30107
4
Real
Analog_In
9
Float
n/a
ADF(Float)
4
1
Avg Flow Rate
30119
4
Real
Analog_In
10
Float
129
0-00h P
ADF(Float)
5
1
Flow Rate Units 30517 8 String String_In 12 UINT16 131 0-00h BD(Byte) 25 8
Raw Flow
30131
4
Real
Analog_In
11
Float
n/a
ADF(Float)
6
1
Raw Flow Units
30537
8
String
String_In
16
UINT16
n/a
BD(Byte)
33
8
Total
30143
4
Real
Analog_In
12
Float
129
33-21h S
ADF(Float)
7
1
Total Units
30557
8
String
String_In
20
UINT16
131
33-21h
BD(Byte)
41
8
Sonic Vel
30155
4
Real
Analog_In
13
Float
n/a
ADF(Float)
8
1
Sonic Vel Units
30577
8
String
String_In
24
UINT16
n/a
BD(Byte)
49
8
Supply Temp
30301
4
Real
Analog_In
14
Float
n/a
ADF(Float)
9
1
Supply Temp Units
30773
8
String
String_In
28
UINT16
n/a
BD(Byte)
57
8
Return Temp
30307
4
Real
Analog_In
15
Float
n/a
ADF(Float)
10
1
Return Temp Units
30781
8
String
String_In
32
UINT16
n/a
BD(Byte)
65
8
Temp Difference
30313
4
Real
Analog_In
16
Float
n/a
ADF(Float)
11
1
Temp Diff Units
30789
8
String
String_In
36
UINT16
n/a
BD(Byte)
73
8
Signal Strength
30165
2
Integer
Analog_In
17
Float
n/a
ADF(Float)
12
1
Sig Strength Units
30593
8
String
String_In
40
UINT16
n/a
BD(Byte)
81
8
Aeration
30171
2
Integer
Analog_In
18
Float
n/a
ADF(Float)
13
1
Aeration Units
30609
8
String
String_In
44
UINT16
n/a
BD(Byte)
89
8
Status/Alarms:
Spacing
10001 1 Bit Coil Binary_In 0 UINT16 n/a DI(Dig In) 1 1
Status/Alarms:
Empty
10002 1 Bit Coil Binary_In 0 UINT16 n/a DI(Dig In) 3 1
Status/Alarms:
Rate
10003 1 Bit Coil Binary_In 0 UINT16 n/a DI(Dig In) 4 1
Status/Alarms:
Fault
10004 1 Bit Coil Binary_In 0 UINT16 n/a DI(Dig In) 5 1
Status/Alarms:
Aeration
10005 1 Bit Coil Binary_In 0 UINT16 n/a DI(Dig In) 6 1
Status/Alarms:
Memory
10006 1 Bit Coil Binary_In 0 UINT16 n/a DI(Dig In) 7 1