Appendix A
A.1 Modbus, EIP, HART & N2 Profile Mappings
F US Clamp-on Communications Protocol Manual
Hardware Installation Manual, 11/2015, A5E34981613-AC
77
C1 Status
/Alarms: Zeroma-
tic
10030 1 Bit Coil Binary_In 0 UINT16 n/a DI(Dig In) 2 1
C1 Delta Time
30179
4
Real
Analog_In
13
Float
n/a
ADF(Float)
8
1
C1 Delta Time
Units
30629 8 String String_In 28 UINT16 n/a BD(Byte) 57 8
C2 Site ID
30505
8
String
String_In
32
UINT16
n/a
BD(Byte)
65
8
C2 Date: Year
30101
2
Integer
Analog_In
0
Float
n/a
ADI(Int)
1
1
C2 Date: Month
30102
2
Integer
Analog_In
1
Float
n/a
ADI(Int)
2
1
C2 Date: Day
30103
2
Integer
Analog_In
2
Float
n/a
ADI(Int)
3
1
C2 Time: Hour 30104 2 Integer Analog_In 3 Float n/a ADI(Int) 4 1
C2 Time: Minute
30105
2
Integer
Analog_In
4
Float
n/a
ADI(Int)
5
1
C2 Time: Second
30106
2
Integer
Analog_In
5
Float
n/a
ADI(Int)
6
1
C2 Inst.Flow
Rate
30111 4 Real Analog_In 14 Float 129 7-07h ADF(Float) 9 1
C2 Avg Flow
Rate
30123 4 Real Analog_In 15 Float 129 2-02h T ADF(Float) 10 1
C2 Flow Rate
Units
30521 8 String String_In 36 UINT16 131 2-02h BD(Byte) 73 8
C2 Total
30147
4
Real
Analog_In
16
Float
129
35-23h Q
ADF(Float)
11
1
C2 Total Units
30561
8
String
String_In
40
UINT16
131
35-23h
BD(Byte)
81
8
C2 Status
/Alarms: Spacing
10041 1 Bit Coil Binary_In 1 UINT16 n/a DI(Dig In) 10 1
C2 Status
/Alarms: Empty
10042 1 Bit Coil Binary_In 1 UINT16 n/a DI(Dig In) 12 1
C2 Status
/Alarms: Rate
10043 1 Bit Coil Binary_In 1 UINT16 n/a DI(Dig In) 13 1
C2 Status
/Alarms: Fault
10044 1 Bit Coil Binary_In 1 UINT16 n/a DI(Dig In) 14 1
C2 Status
/Alarms: Aeration
10045 1 Bit Coil Binary_In 1 UINT16 n/a DI(Dig In) 15 1
C2 Status
/Alarms: Memory
10046 1 Bit Coil Binary_In 1 UINT16 n/a DI(Dig In) 16 1
C2 Status
/Alarms: Makeup
10047 1 Bit Coil Binary_In 1 UINT16 n/a DI(Dig In) 17 1
C2 Status
/Alarms: Interface
10048 1 Bit Coil Binary_In 1 UINT16 n/a DI(Dig In) 18 1
C2 Status
/Alarms: Zeroma-
tic
10050 1 Bit Coil Binary_In 1 UINT16 n/a DI(Dig In) 11 1
C2 Percent
Deviation
30191 4 Real Analog_In 17 Float n/a ADF(Float) 12 1
C2 Deviation
Units
30649 8 String String_In 43 UINT16 n/a BD(Byte) 89 8