Appendix A
A.1 Modbus, EIP, HART & N2 Profile Mappings
F US Clamp-on Communications Protocol Manual
86 Hardware Installation Manual, 11/2015, A5E34981613-AC
Date: Day
30103
2
Integer
Analog_In
2
Float
n/a
ADI(Int)
3
1
Time: Hour
30104
2
Integer
Analog_In
3
Float
n/a
ADI(Int)
4
1
Time: Minute
30105
2
Integer
Analog_In
4
Float
n/a
ADI(Int)
5
1
Time: Second
30106
2
Integer
Analog_In
5
Float
n/a
ADI(Int)
6
1
C1 Inst.Flow Rate
30109
4
Real
Analog_In
6
Float
129
6-06h
ADF(Float)
1
1
C1 Avg Flow Rate
30121
4
Real
Analog_In
7
Float
129
1-01h P
ADF(Float)
2
1
C1 Flow Rate Units
30517
8
String
String_In
4
UINT16
131
1-01h
BD(Byte)
9
8
C1 Total 30145 4 Real Analog_In 8 Float 129 34-22h
S
ADF(Float) 3 1
C1 Total Units
30557
8
String
String_In
8
UINT16
131
34-22h
BD(Byte)
17
8
C1 Status/Alarms:
Spacing
10021 1 Bit Coil Binary_In 0 UINT16 n/a DI(Dig In) 1 1
C1 Status/Alarms:
Empty
10022 1 Bit Coil Binary_In 0 UINT16 n/a DI(Dig In) 3 1
C1 Status/Alarms:
Rate
10023 1 Bit Coil Binary_In 0 UINT16 n/a DI(Dig In) 4 1
C1 Status/Alarms:
Fault
10024 1 Bit Coil Binary_In 0 UINT16 n/a DI(Dig In) 5 1
C1 Status/Alarms:
Aeration
10025 1 Bit Coil Binary_In 0 UINT16 n/a DI(Dig In) 6 1
C1 Status/Alarms:
Memory
10026 1 Bit Coil Binary_In 0 UINT16 n/a DI(Dig In) 7 1
C1 Status/Alarms:
Makeup
10027 1 Bit Coil Binary_In 0 UINT16 n/a DI(Dig In) 8 1
C1 Status/Alarms:
Interface
10028 1 Bit Coil Binary_In 0 UINT16 n/a DI(Dig In) 9 1
C1 Status/Alarms:
Zeromatic
10030 1 Bit Coil Binary_In 0 UINT16 n/a DI(Dig In) 2 1
Temperature 1
30293
4
Real
Analog_In
9
Float
n/a
ADF(Float)
4
1
Temp 1 Units
30757
8
String
String_In
12
UINT16
n/a
BD(Byte)
25
8
Aux Input 1
30285
4
Real
Analog_In
10
Float
n/a
ADF(Float)
5
1
Aux 1 Type
30813
8
String
String_In
16
UINT16
n/a
BD(Byte)
33
8
Aux Input 2 30287 4 Real Analog_In 11 Float n/a ADF(Float) 6 1
Aux 2 Type
30817
8
String
String_In
20
UINT16
n/a
BD(Byte)
41
8
C1 Percent Devia-
tion
30189 4 Real Analog_In 12 Float n/a ADF(Float) 7 1
C1 Deviation Units
30645
8
String
String_In
24
UINT16
n/a
BD(Byte)
49
8
C2 Site ID
30505
8
String
String_In
28
UINT16
n/a
BD(Byte)
57
8
C2 Inst.Flow Rate
30111
4
Real
Analog_In
13
Float
129
7-07h
ADF(Float)
8
1
C2 Avg Flow Rate
30123
4
Real
Analog_In
14
Float
129
2-02h T
ADF(Float)
9
1
C2 Flow Rate Units
30521
8
String
String_In
32
UINT16
131
2-02h
BD(Byte)
65
8
C2 Total 30147 4 Real Analog_In 15 Float 129 35-23h
Q
ADF(Float) 10 1
C2 Total Units
30561
8
String
String_In
36
UINT16
131
35-23h
BD(Byte)
73
8
C2 Status/Alarms:
Spacing
10041 1 Bit Coil Binary_In 1 UINT16 n/a DI(Dig In) 10 1
C2 Status/Alarms:
Empty
10042 1 Bit Coil Binary_In 1 UINT16 n/a DI(Dig In) 12 1
C2 Status/Alarms:
Rate
10043 1 Bit Coil Binary_In 1 UINT16 n/a DI(Dig In) 13 1