Commissioning
6.2 Navigating the menu structure
SITRANS FUS080 transmitter
Operating Instructions, 07/2012, A5E03059912-02
31
6.2 Navigating the menu structure
Use the push button to navigate between the following menu items:
Table 6- 3 Menu items
Menu Parameter Display example Comments
Menu 1 Flow volume totalizer 1
Factory preset is forward
volume flow.
The battery symbol shows
full.
Menu 2 Flow volume totalizer 2
Factory preset for reverse
flow.
Negative values indicate
reverse flow calculation.
Menu 3 Actual flow rate
Negative values indicate
reverse flow calculation..
Menu 4 Alarm codes
Each code refers to a
specific alarm.
Menu 5 Display test
Check of all segments.
Display toggles between all
segments on/off.
6.3 Start-up routine
1. Power-up device.
2. Reset battery status indicator as described below (battery-powered versions only).
Resetting the battery counter
Note
The reset can also be carried out via SIMATIC PDM.
When new batteries are installed and the plug is connected, the transmitter start-up routine
begins. The display shows the active software version, e.g. 2.03.
After ten seconds the message "reset.bat" will appear.