Parameter lists
A.4 Meter setup
SITRANS FUS080 transmitter
78 Operating Instructions, 07/2012, A5E03059912-02
A.4 Meter setup
Table A- 4 Meter setup parameters
Modbus
Address
Parameter Default
value
Value
range
Access
level
Description
Meter Setup
40179 307 Flow velocity offset 0 m/s -10 ... 10
m/s
HW key Velocity added to measured flow
velocity
40182 310 Calibration factor 1.0 0 ... 2 R/W This calibration factor will be calculated
at the factory with wet-calibration.
For FUS080-SONOKIT (retrofit)
installations this parameter should be
calculated by the pipe geometric tool
(see 'Pipe geo. assistant' in 'Device'
menu)
40151 311 Adjustment Factor 1 - 2 ... 2 R/W Meter correction factor for customer
adjustment of the calculated flow
value. Can be used at installations
where a reference meter is used to get
reference to the true flow rate
40196 312 Transducer cable
length
Product
dependent
0 ... 200
m
R/W Cable length (m) from sensor to
transmitter
40173 372 Filter time constant Product
dependent
0 ... 100 s R/W General time filter for flow
measurement. Filter constant is the
time that must pass before the filter's
ouput value is at 70% of the change of
its input value. Higher number gives a
slower and more stable flow signal.
40184 380 Protect linearization
from user access.
No No, Yes Read Protection of the linearization
parameters. It is decided by the order
number and cannot be changed.
The linearization parameters are listed
in the device menu 'Linearization'
Totalizer
40673 400 Flow direction totalizer
1
Forward Forward,
Reverse,
Net
R/W Calculation principle on flow direction
for forward, reverse or net flow
40675 401 Totalizer 1 change date Last
change
date
dd-mm-
yyyy;
hh:mm:ss
Read Date and time when totalizer 1 function
was changed
40674 410 Flow direction totalizer
2
Reverse Forward,
Reverse,
Net
R/W Calculation principle on flow direction
for forward - reverse or net flow
40678 411 Totalizer 2 change date Last
change
date
dd-mm-
yyyy;
hh:mm:ss
Read Date and time when totalizer 2 function
was changed