SITRANS FUS080 transmitter
Operating Instructions, 07/2012, A5E03059912-02
61
Technical data
10
10.1 SITRANS FUS080
Table 10- 1 Technical data, FUS080
Description Specification
Enclosure design/material Fiber glass reinforced polyamide in light-gray color
Enclosure IP67 according to EN 60529 and DIN 40050 (NEMA 4X/6)
Wall mounting kit Terminal box made of fiber glass reinforced polyamide in light-gray
color with 2 + 2 cable glands (output, supply, and transducer
cables) and a stainless steel bracket for wall or pipe mounting
Cable glands In wall mounting kit:
4 x M20 polyamide cable glands (2 for mains and output
cables, 2 for the transducer coaxial cables)
Ambient temperature -5 °C …+60 °C (23 °F…140 °F)
Storage temperature −40 °C…+85 °C (−40 °F…+185 °F)
Transducer / sensor cables
Coaxial cable, impedance 75 Ohm, ∅ app. 6mm;
Cable length: Max. 30 meter between transmitter and
transducer (factory sets 15 or 30 m (49.21 or 98.43 ft)
Mechanical vibration 2 g, 1…800 Hz sinusoidal in all directions according to IEC 68-2-6
Power supply Battery:
Replaceable 3.6 V LiSOCl (Lithium Thionyl Chloride)
Double battery pack 32 Ah or single back-up battery 16 Ah;
Battery change interval: 6 years at 60 °C (140 °F) operation
(depending on used functions)
Mains:
87 … 265 V AC (50 … 60 Hz)
Display
LCD, 8 digits, additional 2 digits and symbols for status
information
Units:
Volume unit: m
3
(default display unit)
Flow unit: m
3
/h (default display unit)
Alarm codes: F 1 to F 9
Push button One push button for toggling between display information
Measuring function
0.5 Hz battery mode
or
15 Hz mains-powered