Siemens SITRANS FUS080 - Parameter Lists; Diagnostic Parameters

Siemens SITRANS FUS080
95 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter lists
A.3 Diagnostic
SITRANS FUS080 transmitter
Operating Instructions, 07/2012, A5E03059912-02
73
Modbus
Address
Parameter Default
value
Value range Access
level
Description
40780 163 Previous settling date 01-01-
2000
Read Previous settling date where value
of totalizer 1 was stored
40783 164 Previous totalizer 1 value 0 dd-mm-yyyy Read Previously stored value of totalizer 1
A.3 Diagnostic
Table A- 3 Diagnostic
Modbus
Address
Parameter Default
value
Value
range
Access
level
Description
Diagnostic
40804 500 Latest service date 01-01-
2000
dd-mm-
yyyy
R/W* Latest service date (can also be used
for date of installation)
40808 501 Operating hours since
power up
0 3.4E+38 h Read Total operation hours since last power
up
40807 503 Numbers of power up 0 0 ... 65535 Read Total number of power-ups since first
power-up.
Alarm
43005 200 Fault status One or
more of
the
following
values: 1,
2, 3, 4, ...
up to 16
Read Fault status
1: Path 1 error
2: Path 2 error
3: Dual slope calibration error
4: Database checksum error
5: Low power warning
6: Flow overload warning
7: Pulse A overload warning
8: Pulse B overload warning
9: Consumption interval error
10: Not used
11: Not used
12: Not used
13: Not used
14: Not used
15: Not used
16: Not used
40346 202 Date of fault log reset Last reset
date
dd-mm-
yyyy,
hh:mm:ss
Read Date of last fault log reset
14 204 Reset the fault log and
faults
No No, Yes R/W Reset the fault log and faults
15 205 Call up acknowledge No No, Yes R/W Select 'Yes' to reset active call-up