Parameter lists
A.1 Identification
SITRANS FUS080 transmitter
70 Operating Instructions, 07/2012, A5E03059912-02
Modbus
Address
Parameter Default
value
Value range Access
level
Description
40135 9 Flowrate unit m
3
/h see appendix
A6
R/W Flow unit as text for actual flowrate.
Change the unit in parameter table if
the device menu 'Unit guide (offline)'
does not list the wanted unit.
Note: The device display can show
'm3/s' unit only - other units cannot be
shown on the display, but will be used
and shown online via PDM.
40129 10 Maximum flow Qmax See
"Dimension
dependent
settings",
SONOKIT 2-
path and
"Dimension
dependent
settings",
SONOKIT 1-
path
R/W Maximum flow
40162 373 Low flow cut-off 0.25 0 ... 10 R/W If the flow comes below this
percentage of Qmax, then the flow
value is set to zero
40008 20 Vendor name Siemens
A/S
Read Siemens A/S Flow Instruments,
Denmark
40001 21 Module type 11 0 ... 14 Read Type of flowmeter
40002 22 Software version 2.03 Software version of the flowmeter
40022 23 Product code
number
Product
dependent
Siemens production sales code
number (the first part of the system
number on the nameplate)
40014 24 System Serial
number
Product
dependent
R/W Siemens production number (the s
econd part of the system number on
the nameplate
40065 25 Transmitter serial
number
Product
dependent
HW key Serial number of the electronics
40073 26 Sensor serial number Product
dependent
Serial number of the sensor
40162 373 Low flow cut-off 0.25 0 ... 10 R/W If the flow comes below this
percentage of Qmax, then the flow
value is set to zero