Messages and Diagnostics
SIWAREX FTA
No.
command errors -
Plausibility error
Base parameter
mode not allowed
Weighing operating mode in DR 4 is not correct. Enter a correct
weighing operating mode.
implausible
The default limit values in DR 4 are not plausible. Limit value 3
may only be operated as a max-limit value (On ≥ Off). Correct
135
Weighing
position cycles not
The number for the tare/zero definition cycle is incorrect
(max. 100). Enter a correct value.
weighing pauses
The default for pauses between the control weighing procedures
is incorrect (max. 100). Correct the definition.
time too long
The emptying overlap time in DR 23 is too large. The maximum
may only correspond with the emptying time that is defined there.
implausible
The limits for tare in DR 23 are not plausible. Tare minimum and
maximum weight may not be less. The tare maximum weight
must be larger than the minimum weight. Correct the entry.
assignment for
automatic logging is
The log text number in DR 23 is incorrect.
Correct the number (0...4).
allowed or unknown
The default for the tare/zero setting mode in DR 23 is incorrect.
Correct the default (0..4).
Fine time must be greater than Inhibition time Fine.
Correct the default in DR 23.
implausible
The default for tolerance ranges TO1, TU1, TO2, TU2 must be
corrected. TU2 must be greater than TU1 and TO2 greater than
TO1. Check parameter definitions in DR 22.