Weighing Functions
SIWAREX FTA
Range of Values / Explanation
simulation
0: Weight simulation inactive
1: Weight simulation value of SIMATIC
2: Weight simulation value of RS232
Other definitions not permitted.
rounding the decimal
places of the process
values
(Float weight values)
0: Round to 0 decimal places
1: Round to 1 decimal place
2: Round to 2 decimal places
3: Round to 3 decimal places
4: Round to 4 decimal places
5: Round to 5 decimal places
6: Round to 6 decimal places
0: Outputs in service operation - Forced
operation not possible
1: Outputs in service operation - Forced
operation possible
output to the SIMATIC
CPU
Various process values are available for
selection after listing.
output to the SIMATIC
CPU
Various process values are available for
selection after listing.
alarm 0
Value 0 - No process alarm generation
Value range 1 – 0FFh
Number of the technical error
Value range 100h – 13Fh
100h+ 0...1Fh Bit-No. NAWI-status bit - coming
100h+ 20h...3Fh Bit-No. AWI Status flag - coming
Value range 200h – 23Fh
200h+ 0...1Fh Bit-No. NAWI status bit - going
200h+ 20h...3Fh Bit-No. AWI status bit - going
alarm 1
Value 0 - No process alarm generation
Value range 1 – 0FFh
Number of the technical error
Value range 100h – 13Fh
100h+ 0...1Fh Bit-No. NAWI-status bit - coming
100h+ 20h...3Fh Bit-No. AWI Status bit - coming
Value range 200h – 23Fh
200h+ 0...1Fh Bit-No. NAWI status bit - going
200h+ 20h...3Fh Bit-No. AWI status bit - going
alarm 2
Value 0 - No process alarm generation
Value range 1 – 0FFh
Number of the technical error
Value range 100h – 13Fh
100h+ 0...1Fh Bit-No. NAWI-status bit - coming