5.20 Programming input signals
CONFIGURATION: 1. system data
(4.4.1) 2. collective line
3. password
4. addressable line
5. SWE330A
6. LON devices
7. serial ports
8. K6 inputs
to define basic functions and alarm organization
to define the conventional lines (only if K3M010 or K3M020 is equipped)
to overwrite the 4 basic passwords
to define the addressable lines / logical detector zones and conTrol zones
for data transfer FC330A PC (see page 70)
to define the floor repeater and control panels
to define the application on the serial ports
to define programmable inputs on K3X0x0 / K6
K6 inputs: 1: ######
(4.4.1.8) 2: ######
3: ######
>Sel. input 4: ######
Display
Possible options
Not used None
to toggle between manned/unmanned External CAC
to activate alarm horns Evacuation
to acknowledge system ACKNOWLEDGE
to reset system RESET
to initiate lamp test lamp test
to signal FAULT from external external FAULT
to disable remote transmission (alarm+fault) DISABLE RT
to signal mains fault from external ext. Fault mains
to signal battery fault from external ext. Fault batt
to signal power fault from external ext. Fault power
to initiate ALARM from external External Alarm
to disable ’fire controls’ (see page 62) DISABLE fire ctrl.