3 Commissioning
3.1 Commissioning procedure
1. Read safety instructions see page 50
2. Check electronic hardware see page 51
3. Switch power on see page 51
4. Select function ‘autom. configuration’ see page 53
5. Read autom. device configuration see page 53
6. Compare number of ‘planned’ with number of ‘seen’ devices
7. If not
equal correct detector network
If equal either
upload device configuration to the configuration tool SWE330A
or
start programming user functions direct via keypad
8. Check all autom. detectors, call points, control in-/outputs
and user texts
see page 56
Work to be done before commissioning can be started
installation of detector lines must be completed
all detector bases must be tested
SynoLINE 600 and control lines must be terminated
all SynoDEC detector heads must be inserted
control unit must be mounted
all accessories must be onsite
mains supply voltage must be available
the zoning must be defined see page 54
listing and order of installation of all SynoLOOP devices see page 125
must be available
Remarks
Date and time of the internal clock are lost when the power is removed from the control
unit (mains and battery).
Do not plug−in or do not connect any add-on cards while the system is under power.
If the configuration tool SWE330A is not used print out the user functions and user texts
when commissioning is completed.
Completing the commissioning work
Commissioning work is completed when:
User application setting is completed
User text editing is completed and checked
All detectors, call points and input/output modules are allocated to the correct ZONE and user text
All detectors, call points, input/output modules and alarm devices have been tested and set to position ’on’
internal clock is set (time and date)
No fault message is reported
Ô The system can now be handed over the customer