3.6 Testing peripheral devices
Automatic detectors and manual call points
Test key
Testing manual call points
Insert test key
Wait until response
indicator flashes
Remove test key
Open the cover of a manual
call point with key
Press button in completely
Wait until response
indicator flashes
Reclose cover
SynoLOOP
Detector tester RE6T
Testing smoke detector Testing heat detector
Set zones to mode ’Detector test’ (see operating menu page 63)
Test all detectors
for a ’Test alarm’ the response indicator on the detector flashes for approx. 10 seconds
SynoLINE
OP....
OH....
HI....
Detector tester RE6
SynoLOOP
SynoLINE
Version «KAC»
Version «DIN»
Activate fire controls
Internal controls External controls
Make sure that the activation
causes no damage to any buil-
ding equipment
Activate each fire control
according to the individual
system configuration and check
for correct allocation