is part of the system configuration. Each installation has its specific zoning. The zoning
requires the knowledge of the precise order of installation of all devices within the line(s).
ZONE
represents the ‘room-address’
alarm events are shown on the ‘zone level’
each zone has its own user text
is part of the logical structure
ELEMENT
represents the ‘detector-address’ within a zone
is always allocated to a zone (automatically done during the linking ‘device to zone’)
can have its own user text instead of the ZONE user text (only in special cases)
DEVICE
physical device (detector, call point, etc.) within the detection line
each device must be linked to a zone
is part of the physical structure
DEVICE
ZONE
ELEMENT
Example
Typical floor layout with linked devices
Presentation of ‘alarm event’ in room 104
1st line zone no. and element no.
2nd line individual user text
01
logical structurephysical
01
Room
101
zone 1
Room
103
zone 3
01 01
Elevator
zone 6
01 02
Room
104
zone 4
01 02 03
Corridor
zone 5
linking
123456789
room 104 zone 4
element 01 + 02
room 102
zone 2
room 101
zone 1
room 103
zone 3
Room
102
zone 2
1
2
3
4
5
6
7
8
9
installed detector line/loop
2nd floor
ALARM zone ###/## / ######
2nd floor room office 104
1 (1)