Siemens Synova FC330A - Page 56

Siemens Synova FC330A
136 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Fire Safety & Security Products
Building Technologies
1583_o_en_−−_3
52
08.2005
Master board K3X030
Keyboard
LCD
Key-lock
switch
K3L070
or
K3G050
mains 115/230VAC
24V supply
Outputs
Inputs
Remote transmission alarm and fault
Loop 1 or stub line 1
pluggable
connecting
terminals
LEDs 1 to 4
RS232-1 application see page 114
sensor (NTC) for temperature
compensation system voltage
Battery
mains fuses
Horn 1 and 2
1
2
6
3
4
5
7
8
9
10
11
12
14
EPROM EP1 (4MB)
EPROM EP2 (2MB or 4MB)
13
50VA
Potentiometer to adjust battery charging
voltage on ’K9’
(115VAC 630mA/T)
315mA/T
Pos. Description Normal state / position
H1/H2 LED ”EARTH FAULT” 0V / 24V” earth fault to 0V or 24V not lit
H8 LED ”5V LOW” 5V supply voltage too low not lit
H7 LED ”5V POWER” 5V supply voltage available lit
H3/H4 LED ”CH1 RXD” (receive) ”TXD” (transmit) of RS232-1 pulsating during communication
H9 LED ”CP” current pulse detector communication pulsating
S1 Momentary switch to restart the system
S2 Momentary switch to ”DELETE alarm counter”
ST8/ST9/ST10 Jumper to select battery make (brand) see page 20
set according battery make
ST9 default (at factory)
ST1 Jumper / removed = watchdog inactive inserted
ST2 Jumper / removed = earth leak detection inactive inserted
ST3 Jumper / set to top = NTC disabled no temperature compensation
inserted to ’bottom’ (at factory)
see page 106
ST7 Jumper / removed = buzzer disabled inserted
ST13 + St14 1)
Supply mode:
Mains (without battery) Jumper ST13 inserted
Mains + Battery (K9) Jumper ST14 inserted
default (at factory)
MP1/MP2 Pins to pickup 5V for RS232/LON converter card K3I080
1) jumper not to change while system is in operation
1
2
3
4
5
6
7
8
9
1
0
1
1
1
2
1
3
1
4