horn on INTERNAL ALARM: 1. inactive
> selected #, change? 2. active
− to define that the control lines ‘horn’ are also
activated during state ‘internal alarm’
− applies for all ‘horn’ control lines
1. horns not activated on ‘inter-
nal alarm’
2. horns activated on ‘internal
alarm’
horn on INTERNAL ALARM: 1.continuous
> #, ch.? 2. pulsating 3.set pulse
− common for all ‘horn’ control lines on internal
alarm
1. continuous signal on alarm
2. pulsating signal on alarm
3. goes to sub-menu ‘pulse
length’
horn on INTERNAL ALARM / phase ACTIVE:
(3..20sec) sel. ##/10 sec change?
− to set the pulse length of phase ACTIVE − value 3 = 0.3sec / 20 = 2sec
− one step = 0.1sec)
− default = 5 (0.5sec)
horn on INTERNAL ALARM / phase INACTIVE:
(3..20sec) sel. ##/10 sec change?
− to set the pulse length of phase INACTIVE − value 3 = 0.3sec / 20 = 2sec
− one step = 0.1sec)
− default = 5 (0.5sec)
al.cont. on INTERNAL ALARM: 1. inactive
> selected #, change? 2. active
− to define that all alarm contacts
(K3X020/K3G050) are also activated on IN-
TERNAL ALARM
1. not activated on internal
alarm
2. activated on internal alarm
DUAL mode: 1. inactive
> selected #, change? 2. active
− to trigger immediately the remote transmission
on alarm of 2 detector zones simulta-
neously during mode ‘manned’
1. ‘DUAL alarm’ not activated
2. ‘DUAL alarm’ activated
LED ISOLATION on mode ’manned’: 1. OFF
> selected #, change? 2. ON
− to define whether LED ’ISOLATION’ on the
front is activated upon mode ’manned’ (re-
quirement by EN54 = ON)
1. not activated on mode
’manned’
2. activated on mode ’manned’
Description alarm organization see page 107/108