05.2006 Parameterizing Steps
Siemens AG 6SE7087-2JD60
SIMOVERT MASTERDRIVES Operating Instructions 9-5
Select "Fixed settings" menu
P366 = ?
P970 = 0
Start parameter reset
0: Parameter reset
1: No parameter change
P060 = 2
Select desired factory setting
0: Standard with PMU, setpoint via MOP (BICO1)
1: Standard with OP1S, setpoints via fixed setpoints (BICO1)
2: Cabinet unit with OP1S, setpoint via fixed setpoints (BICO1)
3: Cabinet unit with PMU, setpoint via MOP (BICO1)
4: Cabinet unit with OP1S and NAMUR terminal strip (SCI),
setpoint via MOP (BICO1)
Note: This parameter was correctly set prior to delivery of
the unit and only needs to be changed in exceptional
cases.
re 0 to 3: In BICO data set 2 activation/deactivation is carried
out via the terminal strip and the setpoint is specified
via fixed setpoint (P405).
P053 = 6
Grant parameter access
6: Parameter changes permitted via PMU and serial interface
SCom1 (OP1S and PC)
Unit carries out parameter
reset and then leaves the
"Fixed settings" menu
Fig. 9-2 Sequence for parameter reset to factory setting