23
Pressing the SUPV ACK key once globally acknowledges all supervisory conditions that exist
within the fire alarm system. In addition, the “SUPERVISORY“ LED changes from flashing to
steady ON and the tone-alert silences.
If global acknowledge is enabled on your system, use the following procedure to acknowledge the
supervisory conditions.
1. Unlock and open the enclosure door. The alphanumeric display shows the supervisory
condition, similar to the following example.
2. Press the SUPV ACK key under the flashing yellow LED. The alphanumeric display shows
the area and type of condition. The tone-alert silences and the yellow LED glows steady.
Read the alphanumeric display. Investigate the problem to determine its cause. Restore or replace
the defective device (switch, wire, notification appliance) in accordance with the manufacturer’s
instructions, or call Simplex to repair the system. When the problem causing the supervisory is
corrected, the supervisory automatically clears and, after a delay, the alphanumeric display
indicates that the system status is normal.
If individual acknowledge is enabled on your system, you need to separately acknowledge each
supervisory condition. Use the following procedure to do this.
1. Unlock and open the enclosure door. The alphanumeric display shows the supervisory
condition, similar to the following example.
19BAcknowledging Supervisory Conditions
76BGlobally
Acknowledging
Supervisory
Conditions
77BIndividually
Acknowledging
Supervisory
Conditions
**SUPERVISORY** Press <ACK> to review
FIRE = 0 PRI2 = 0 SUPV = 1 TRBL = 0
REVERE BASEMENT NORTH WING ROOM 31
SPRINKLER MONITOR ABNORMAL
**SUPERVISORY** Press <ACK> to review
FIRE = 0 PRI2 = 0 SUPV = 1 TRBL = 0

Table of Contents

Other manuals for Simplex 4100ES

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100ES and is the answer not in the manual?

Simplex 4100ES Specifications

General IconGeneral
TypeFire Alarm Control Panel
DisplayLCD
Battery BackupYes
Model4100ES
ManufacturerSimplex
Communication ProtocolOptional Ethernet
Signaling Line Circuits (SLCs)Up to 10
Notification Appliance Circuits (NACs)Up to 10
Agency ListingsUL, FM, CSFM, MEA
Max Relay Circuits20
Communication PortsEthernet
Operating Temperature32°F to 120°F (0°C to 49°C)
HumidityUp to 93% RH, non-condensing

Related product manuals