1.1.4 Address Settings for Simplex® Addressable Bases & Devices
Note: MAPnet devices highest address is 127.
DIP Switches 5-8
0000
1000
0100
1100
0010
1010
0110
1110
0001
1001
0101
1101
0011
1011
0111
1111
DIP Switches 1 - 4
0000
0
16
32
48
64
80
96
112
128
144
160
176
192
208
224
240
1000
1
17
33
49
65
81
97
113
129
145
161
177
193
209
225
241
0100
2
18
34
50
66
82
98
114
130
146
162
178
194
210
226
242
1100
3
19
35
51
67
83
99
115
131
147
163
179
195
211
227
243
0010
4
20
36
52
68
84
100
116
132
148
164
180
196
212
228
244
1010
5
21
37
53
69
85
101
117
133
149
165
181
197
213
229
245
0110
6
22
38
54
70
86
102
118
134
150
166
182
198
214
230
246
1110
7
23
39
55
71
87
103
119
135
151
167
183
199
215
231
247
0001
8
24
40
56
72
88
104
120
136
152
168
184
200
216
232
248
1001
9
25
41
57
73
89
105
121
137
153
169
185
201
217
233
249
0101
10
26
42
58
74
90
106
122
138
154
170
186
202
218
234
250
1101
11
27
43
59
75
91
107
123
139
155
171
187
203
219
235
251
0011
12
28
44
60
76
92
108
124
140
156
172
188
204
220
236
252
1011
13
29
45
61
77
93
109
125
141
157
173
189
205
221
237
253
0111
14
30
46
62
78
94
110
126
142
158
174
190
206
222
238
254
1111
15
31
47
63
79
95
111
127
143
159
175
191
207
223
239
255
Detectors preset at address 255
UP = 1 (ON)
DOWN = 0 (OFF)

Table of Contents

Other manuals for Simplex 4100+

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100+ and is the answer not in the manual?

Simplex 4100+ Specifications

General IconGeneral
TypeAddressable Fire Alarm Control Panel
SLC LoopsUp to 10
Operating Temperature32°F to 120°F (0°C to 49°C)
Humidity Range10% to 93% non-condensing
DisplayLCD
CommunicationEthernet
Power Supply120/240 VAC, 50/60 Hz
Battery Backup24 VDC
NAC OutputsExpandable
Releasing CapabilityYes, with releasing modules
Max Notification Appliance Circuits (NACs)Varies by modules
Max Releasing Circuits10
Communication PortsEthernet
Max Devices3, 000