1.1.3.1.4 Bad Answer
Description:
The panel is getting a response from the displayed address that sometimes does not match the device
programmed to that address.
Possible causes:
Two devices are programmed with the same address.
These devices will most likely be two different device types.
Water damaged device, or wiring.
Electrical Interference
Suggested solutions:
No
Yes
Yes
No
Find other device on
Loop with same
address.
Fault changed to
„WRONG DEVICE‟
Bad Answer Fault clears
and no fault present at
device address
Fault changed to „no
answer‟
Remove the device/base at
the known address
Find other device on
Loop with same
address.
Device will probably
be in „NO ANSWER‟
fault
Replace device or
Sensor

Table of Contents

Other manuals for Simplex 4100+

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Simplex 4100+ and is the answer not in the manual?

Simplex 4100+ Specifications

General IconGeneral
TypeAddressable Fire Alarm Control Panel
SLC LoopsUp to 10
Operating Temperature32°F to 120°F (0°C to 49°C)
Humidity Range10% to 93% non-condensing
DisplayLCD
CommunicationEthernet
Power Supply120/240 VAC, 50/60 Hz
Battery Backup24 VDC
NAC OutputsExpandable
Releasing CapabilityYes, with releasing modules
Max Notification Appliance Circuits (NACs)Varies by modules
Max Releasing Circuits10
Communication PortsEthernet
Max Devices3, 000

Related product manuals