Y070.020/GB Page 41
Operation instructions
SIPOS 5 PROFITRON, HiMod
5
Commissioning
5 Commissioning
„busy…“ is then displayed for approx. 4 ° s. During this
period, the non-intrusive position encoder is initialized.
The rst end position is then set and the system
changes to setting the other end position. Im Display
erscheint „move to cl.pos.“. Depending on the preset
cut-off mode of the second end position, the following is
displayed in the second line:
– for travel-dependent cut-off mode „press E-button“;
or
– for torque-dependent cut-off mode „until TL reached“.
Continue with operation step 6.
busy…
6. Move the actuator to the other end position:
Depending on whether the cut-off mode for the end posi-
tion is travel-dependent or torque-dependent, select the
following operation sequence.
move to cl.pos.
REV/STRO 0,0
Travel-dependent cut-off mode:
In the second display line either „press E-button“ or,
depending on the actuator type:
– REV/STRO for rotary actuator,
– STRO [mm] for linear actuator,
– < [°] for part-turn actuator,
is displayed.
move to cl.pos.
press E-button
a) Use the CLOSE
button (OPEN button for setting
in OPEN direction) to move the actuator, until the
valve has reached the end position. The travel is
indicated in the second display line.
Pay attention to the valve during operation.
Note: If the cut-off was torque-dependent due to a
block, e.g. in case of a sluggish MOV, an unfavo-
rable torque curve (cancel by pressing the and
buttons simultaneously), this is indicated by „TL-
OPEN activ“ or „TL-CLOSE activ“ in the second line.
The same applies to approaching the mechanical
end stop (return to the desired end position using
the or buttons).
% open close
REV/STRO 2,1
b) Once the end position has been reached, con rm af-
ter approx. 2 s. with the ENTER button. The display
con rms the correct setting.
Continue with operation step 7.
adjustment
ok!
Torque-dependent cut-off mode:
In the second display line either „until TL reached“ or,
depending on the actuator type:
– REV/STRO for rotary actuator,
– STRO [mm] for linear actuator,
– < [°] for part-turn actuator,
is displayed.
move to cl.pos.
until TL reached
Hold down CLOSE
button (OPEN button for setting
in OPEN direction) for more than 2 s.
The actuator moves automatically until reaching the
end position. The actuator moves then shortly in the
opposite direction, to return to the end position again.
adapting cl.pos.
busy…
The display con rms the correct setting.
endpos. adjustm.
OK!
7. Press ENTER button. The actuator changes to the „end-
pos. adjust“ parameter in the menu.
endpos. adjust