Operation instructions
SIPOS 5 PROFITRON, HiMod
Page 56 Y070.020/GB
7 Status and fault signals, diagnosis
7
Status and fault signals, diagnosis
Parameter Messages Explanation
remote cntr by
PrCntr CurrInp Process controller with setpoint via analog process setpoint input.
PrCntr bus inp Process controller with setpoint via eldbus.
PrCntr fix setp. Process controller with xed setpoint.
PosCntr CurrInp Positioner with setpoint via analog setpoint input.
PosCntr bus inp. Positioner with setpoint via eldbus.
tri-threshold Control via analog setpoint input:
0 – 30 % = CLOSE, 30 – 70 % = STOP, 70 – 100 % = OPEN.
PermCont BinInp Permanent contact signal via binary inputs with OPEN and CLOSE com-
mands.
PermCont bus Permanent contact signal via eldbus with OPEN and CLOSE com-
mands.
PulsCont BinInp Pulse contact signal via binary inputs (OPEN, CLOSE, and STOP).
two-wire-control Control via OPEN input.
proportion. conv Proportional operation conventionally via binary inputs.
proportion. bus Proportional operation via eldbus.
inter.cont.CLOSE
...%, activ The actuator is within the range 0 % to ... % of the travel.
...%, non-activ The actuator is not within in the range 0 % to ... % of the travel.
inter.cont. OPEN
...%, activ The actuator is within in the range ... % to 100 % of the travel.
...%, non-activ The actuator is not within in the range ... % to 100 % of the travel.
setpoint
... % The current setpoint value is ... % of the set analog signal range, or of
the standard for eldbus control.
proc. act. value
... % The current process actual value is ... % of the analog signal range of
the sensor.
(Indication only appears if the process controller is enabled.)
Analog input 1
... % The current value is ... % of the set analog signal range. (position set-
point, process setpoint or connected external sensor.)
Analog input 2
... % The current value is ... % of the set analog signal range. (output speed
setpoint, actual process value or connected external sensor.)
binary inputs
CL OP STOP EM CLOSE, OPEN, STOP and EMERGENCY signals active.
(Only active signals are displayed.)
no signal CLOSE, OPEN, STOP and EMERGENCY signals not active.
motor temperat.
...°C max 155°C The current motor temperature = ... ° C.
(not for 2SG5…).
electronics temp
...°C Temperature within electronics unit housing.
actual speed
0 /min Current output speed. Indication only appears for rotary actuator.
curr. act. Speed
0 mm/min Current positioning speed. Indication only appears for linear actuator.
curr. act. time
0 s Current positioning time. Indication only appears for part-turn actuator.
position cntr
enabled Positioner is enabled (option).
disabled Positioner is not enabled.
proc. Controller
enabled Process controller is enabled (option).
disabled Process controller is not enabled.
an. speed setpt.
enabled External analog output speed setpoint is enabled (option).
disabled External analog speed setpoint* is not enabled.
speed curve
enabled Travel-dependent output speed adjustment* is enabled (option).
disabled Travel-dependent output speed adjustment* is not enabled.
prop / split
enabled Proportional/split range function is enabled (option).
disabled Proportional/split range function is not enabled.
pos. time curve
enabled Travel-dependent freely adjustable positioning times are enabled
(option).
disabled Travel-dependent freely adjustable positioning times are not enabled.
Bluetooth
valid Bluetooth module detected. Display appears only if Bluetooth is availa-
ble.
___________________________
* Output speed is synonymous to positioning speed (linear actuator 2SB5…) and positioning time
(part-turn actuator 2SC5…/2SG5…).