- 30 -
Pushing speed
Minimum value to
“Max force” of the
basic parameter
(*1)
* Effective only for the pushing operation (when the value for the “Pushing
force” is from 1to 100).
This defines the movement speed during the pushing operation. If this
Speed is too high, it may cause damage to the actuator or work piece due to
impacts. Therefore, enter a value within the range appropriate for the
actuator. (Unit: mm/s)
* Please refer to the actuator manual for the appropriate range of the speed.
* For the positioning operation, this value is ignored.
Moving force
* 1
The setting to define the maximum torque during the positioning operation.
Enter a value within the range appropriate for the actuator. (Unit: %).
* Please refer to the actuator manual for the appropriate range of the speed.
Area1
“Stroke (-)” to
“Area2” of step
data
Area2
“Area1” of step
data to “Stroke (+)”
of the basic
parameter
The setting to define the conditions where the AREA output will be turned ON
(Unit: mm).
If the current position is within the range between the Area1 and Area2, the
AREA output will be turned ON.
* If Area1 >Area2, the alarm “Step Data ALM1” will be activated.
(However,no alarm is generated if “Area1”= “Area2”= 0, the AREA output
will be turned OFF)
In position
* 1
The functions of this will be different between the pushing operation and the
positioning operation.
* Positioning operation: Positioning range (Unit: mm)
* Pushing operation: Pushing distance (Unit: mm)
Operation Description
Positioning
operation
This is the setting to define the conditions where
the INP output will be turned ON.
When the actuator enters within this range from
the target position, the INP will be turned ON.
(It is unnecessary to change this from the initial
value.)
If it is required to get a signal before the actuator
completes the positioning operation, this value
should be larger.
* The INP output will be turned on. Target position
- in position actuator position target
position + in position
Pushing
operation
This is the setting to define the distance pushed by
the actuator during the pushing operation.
When the actuator pushed exceeding this
distance, the pushing operation will end.
In case of such stop exceeding the pushing
distance, the INP will not be turned ON.
* 1: The range varies depending on the actuator. Please refer to the manual of the actuator for more
details.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Corporation LECP6 Series and is the answer not in the manual?

SMC Corporation LECP6 Series Specifications

General IconGeneral
BrandSMC Corporation
ModelLECP6 Series
CategoryController
LanguageEnglish

Related product manuals