Chapter 5 Display and Setting of Various Functions
5.5 Advanced setting mode
HRR Series
5-42
Communication error alarm detection time
26. Press the [▼] key. Displays screen for setting the communication error alarm detection
time.
Time (sec.) to generate alarm AL29: Communication error can be changed.
Setting range: 0 to 600sec. (Initial value: 30sec.)
Time for pump to continue operation when alarm is generated.
27. Press the [▼] key. Displays screen for setting the time for the pump to continue
operation when an alarm is generated.
Setting range: 0 to 9999sec. (Initial value: 0sec.)
Continuation of the pump operation
For some alarms, the pump can continue to operate even when the alarm is
generated by setting this time. The table below shows the alarms for which isolated
pump operation is available.
.
.
Isolated operation of the pump finishes when the one of following conditions is
satisfied.
(1) Pump operation reached the time for isolated operation when alarm is generated.
(2) Pump reached the temperature for isolated operation when alarm is generated.
SEC
Communication error alarm detection time
COMM TIME(Alternately displayed)
SEC
Time for isolated operation of the pump
PUMP TIME(Alternately displayed)

Table of Contents

Other manuals for SMC Networks HRR012-A*-20 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks HRR012-A*-20 Series and is the answer not in the manual?

SMC Networks HRR012-A*-20 Series Specifications

General IconGeneral
BrandSMC Networks
ModelHRR012-A*-20 Series
CategoryChiller
LanguageEnglish

Related product manuals