Chapter 5 Display and Setting of Various Functions
5.21 Alarm Customizing Function HRSH Series
5-52
5.21.2 Setting and checking of the alarm customizing function
The table below shows the set items of the alarm customizing function and
the default settings.
Table 5.21-5 Default settings of the alarm customizing function (1/3)
Display
Content
Alarm
Change
Default
1
Code
Alarm name
Operation setting when
"Low level in tank" alarm
is generated
AL01
Low level in tank
Product operation
while the alarm is
being generated
A.STP
Operation setting when
"Detection temp. for the
circulating fluid discharge
temp. rise" alarm is
generated
AL03
Circulating fluid
discharge temp. rise
Product operation
while the alarm is
being generated
A.RUN
Threshold temperature
setting for "Detection
temp. for the circulating
fluid discharge temp. rise"
alarm
Alarm threshold
40.0
o
C
(104.0
o
F)
(----)
Operation setting when
"Detection temp. for the
circulating fluid discharge
temp. drop" alarm is
generated
AL04
Circulating fluid
discharge temp. drop
Product operation
while the alarm is
being generated
A.RUN
Threshold temperature
setting for "Detection
temp. for the circulating
fluid discharge temp.
drop" alarm
Alarm threshold
1.0
o
C
(33.8
o
F)
(----)
Operation setting when
"Circulating fluid
discharge pressure rise"
alarm is generated
AL08
Circulating fluid
discharge pressure
rise
Product operation
while the alarm is
being generated
ASTP
Threshold pressure
setting for "Circulating
fluid discharge pressure
rise" alarm
Alarm threshold
0.70 MPa
(102 PSI)
or
1.00 MPa
(145 PSI)
(----)
Operation setting when
"Circulating fluid
discharge pressure
decrease" alarm is
generated
AL09
Circulating fluid
discharge pressure
drop
Product operation
while the alarm is
being generated
A.STP
Threshold pressure
setting for "Circulating
fluid discharge pressure
decrease" alarm
Alarm threshold
0.03 MPa
(4 PSI)
or
0.05 MPa
(7 PSI)
(----)
Operation setting when
"Communication error"
alarm is generated
AL19
Communication error
Product operation
while the alarm is
being generated
OFF
Threshold monitoring time
setting for
"Communication error"
Alarm threshold
----
(30)
1: See “Table 5.21-1 Default alarm settings and customizing (1/4) to (4/4)” for more details of the default
settings.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks HRSH Series and is the answer not in the manual?

SMC Networks HRSH Series Specifications

General IconGeneral
BrandSMC Networks
ModelHRSH Series
CategoryChiller
LanguageEnglish

Related product manuals