HRX-OM-Q026
Chapter 5 Display and Setting of Various Functions
HRSH Series 5.21 Alarm Customizing Function
5-57
Setting/Checking: Operation setting when "Circulating fluid discharge temp. drop" alarm is generated
8. Press the [SEL] key once.
Operation setting screen when "Circulating fluid discharge temp. drop" alarm is generated
appears on the digital display.
Set the product operation when "Circulating fluid discharge temp. drop" alarm is generated with
[▲] key or [▼] key, and press [SEL] key to enter.
9. Set the product operation when "Circulating fluid discharge temp. drop" alarm is
generated with [▲] key or [▼] key, and press [SEL] key to enter.
T Table 5.21-11 Operation setting when “Circulating fluid discharge temp. drop” alarm is generated
This alarm is not detected.
Operation continues when this alarm is generated.
Operation stops when this alarm is generated.
Setting/Checking: Threshold detecting temperature setting for "Circulating fluid discharge temp. drop" alarm generation
10. Press the [SEL] key once.
Threshold detecting temperature setting screen for "Circulating fluid discharge temp. drop"
alarm generation appears on the digital display.
11. Set the threshold detecting temperature for "Circulating fluid discharge temp. drop"
alarm generation with [▲] key or [▼] key, and press [SEL] key to enter.
Table 5.21-12 Threshold detecting temperature for "Circulating fluid discharge temp. drop" alarm
Setting/checking of the alarm is impossible when
the "Circulating fluid discharge temp. drop" alarm
is set OFF.
Sets threshold detecting temperature for
"Circulating fluid discharge temp. drop" alarm
Setting temperature unit for Centigrade: 0.1
o
C
Setting temperature unit for Fahrenheit: 0.1
o
F