HRX-OM-Q026
Chapter 5 Display and Setting of Various Functions
5.21 Alarm Customizing Function HRSH Series
5-60
Setting/Checking: Operation setting when "Communication error" alarm is generated
20. Press the [SEL] key once.
Operation setting screen when "Communication error" alarm is generated appears on the digital
display.
21. Set operation when "Communication error" alarm is generated with [▲] key or [▼] key,
and confirm by pressing “SEL”.
Table 5.21-17 Operation setting when “Communication error” alarm is generated
This alarm is not detected.
Operation continues when this alarm is generated.
Operation stops when this alarm is generated.
Setting/Checking: Threshold monitoring time setting for "Communication error"
22. Press the [SEL] key once.
Monitoring time setting screen for "Communication error" alarm appears on the digital display.
23. Set monitoring time for "Communication error" alarm with [▲] key or [▼] key, and
confirm by pressing “SEL”.
Table 5.21-18 Monitoring time for "Communication error" alarm setting
Setting/checking of the alarm is impossible when the
"AS11 Communication error" alarm is set OFF.
Monitoring time for “Communication error” is set.
Setting unit: 1 second
Setting/Checking: Operation setting when "Contact input 1 signal detection" alarm is generated
24. Press the [SEL] key once.
Operation setting screen when "Contact input 1 signal detection" alarm is generated appears on
the digital display.