Chapter 5 Display and Setting of Various Functions
HRSH Series 5.21 Alarm Customizing Function
5-61
25. Set the product operation when "Contact input 1 signal detection" alarm is generated
with [▲] key or [▼] key, and press [SEL] key to enter.
Table 5.21-19 Operation setting when "Contact input 1 signal detection" alarm is generated
Set value
Explanation
Default
This alarm is not detected.
Operation continues when this alarm is generated.
Operation stops when this alarm is generated.
Setting/Checking: Operation setting when "Contact input 2 signal detection" alarm is generated
26. Press the [SEL] key once.
Operation setting screen when "Contact input 2 signal detection" alarm is detected appears on
the digital display.
27. Set the product operation when "Contact input 2 signal detection" alarm is generated
with [▲] key or [▼] key, and press [SEL] key to enter.
Table 5.21-20 Operation setting when "Contact input 2 signal detection" alarm is generated
Set value
Explanation
Default
This alarm is not detected.
Operation continues when this alarm is generated.
Operation stops when this alarm is generated.
Setting/Checking: Operation when "DC line fuse cut" alarm is generated
28. Press the [SEL] key once.
Operation setting screen when "DC line fuse cut" alarm is generated appears on the digital
display.
PV
SV
PV
SV

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks HRSH150-A*-40 Series and is the answer not in the manual?

SMC Networks HRSH150-A*-40 Series Specifications

General IconGeneral
BrandSMC Networks
ModelHRSH150-A*-40 Series
CategoryChiller
LanguageEnglish

Related product manuals