Alarm reset and interruption of operation
When RESET is turned ON during operation, the speed decreases at
maximum deceleration of the basic parameter until the actuator stops.
INP and OUT0 to OUT10 are OFF. (However, if the actuator is stopped
within the in-position range, the INP will be turned ON).
An Alarm is reset when the RESET signal is turned ON if an alarm has
been generated. (Some alarms cannot be reset by the RESET
command).
(1) Do not command SETUP or DRIVE while the RESET input is ON.
The actuator may make unexpected movements.
(2) If the RESET input is ON during a return to origin operation, return
to origin may not be available when the RESET input is turned OFF.
In this case, turn on the servo, and then turn on the SETUP input.
Servo ON instruction
When SVON is ON, the servo motor for all axes will be turned ON.
Note1)
When SVON is OFF, the servo motor will be turned OFF.
Note 1) When power is supplied, it may take up to 20 seconds from Servo ON to SVRE ON,
depending on the actuator position or conditions.