- 18 - 
 
 
(3) Specify the path of the JXCP1 GSDML file and click the [Install] button. 
(The GSDML file for JXCP1 can be downloaded from the SMC website (http://www.smcworld.com). 
 
 
Fig.4.3 Installation of GSDML file 
 
4.3 Addition of JXCP1 controller to PROFINET network 
(1) Start [HW Config] from STEP7(SIMATIC Manager). (Refer to 4.2(1).) 
 
Add the appropriate master (PLC) and the PROFINET bus to the hardware configuration screen. 
(please refer to the STEP 7 user manual for instructions). 
 
Locate the JXCP1 controller icon in the hardware catalogue (right screen), it is under [PROFINET IO], 
[Additional Field Device], [Controllers], [SMC JXC]) 
Drag the icon from the hardware catalogue and drop it on the PROFINET-IO-System line 
(PROFINET network). 
 
 
Fig. 4.4 Addition of JXCP1 to PROFINET network