Controller 
temperatur
e exceeded 
set range. 
(01-146) 
<Details> The temperature around the power element of the controller is 
too high. 
<Countermeasures> Make improvements so that the temperature around 
the controller is kept appropriate. 
Controller 
supply 
voltage is 
outside set 
range. 
(01-147) 
<Contents> The control power supply voltage within the controller is outside 
the set range. 
<Countermeasure> Make sure that the voltage supplied to the control 
power (C24V) of the controller is appropriate. 
If a single power supply is used for both the control power and the 
motor power, or the power supply is "inrush-current control type", a 
power voltage drop may be caused due to a voltage drop during 
acceleration/deceleration. 
<Contents> The alarm may be caused by regenerative power depending on 
the method of operation of the actuator. 
<Countermeasure> Make sure that the operating conditions are within the 
specifications. 
Please refer to the manual or the catalogue of the actuator for the 
method of operation of the actuator. 
Current 
limit is 
exceeded 
(01-148) 
<Contents> The output current accumulated value exceeds the specified 
value. 
<Countermeasure> Make sure there are no obstructions that interfere with 
the actuator movement. Also, make sure that the load, speed, acceleration 
and deceleration are within the range of the actuator. 
The target 
position 
was not 
reached 
within the 
set time 
limit 
(01-149) 
<Content> Failed to reach the set position within the set time limit. 
<Countermeasure> Make sure there are no obstructions that interfere with 
the actuator movement. Also, make sure that the load, speed, acceleration 
and deceleration are within the range of the actuator. 
Communic
ation error. 
(01-150) 
<Contents> The connection with the higher-level devices (such as the PC 
and teaching box) is disconnected. 
<Contents> The connection with the higher-level devices (such as the PC 
and teaching box) is disconnected. 
In case of the communication failure of PC or teaching box, resetting of 
alarm by PC or teaching box is possible after connecting again. 
Turn OFF 
and ON the 
power 
supply for 
the 
controller 
<Contents> Abnormality in communication with the encoder. 
<Countermeasure> Check the connection of the actuator cable. 
Unable to 
find motor 
phase in 
set time. 
(01-193) 
Turn OFF 
and ON the 
power 
supply for 
the 
controller 
<Contents> Unable to find the motor phase within the set time. 
(When the servo motor is turned ON (“SVON” turns ON) for the first time 
after the power is applied, the actuator needs to move a little to find the 
motor phase. However, if this actuator movement is prevented, this alarm 
will be activated.) 
<Countermeasure> Make sure there are no obstructions that interfere with the 
actuator movement and then turn ON the servo motor (“SVON” turns ON).