7. ENVIRONMENTAL CONDITIONS
Humidity
80 % humidity without condensation at 55°C
95 % humidity without condensation at 40°C
Temperature
-20 +40°C without de-rating
40 °C < t ≤ 70 °C with de-rating (see Technical Characteristics)
Altitude
Up to 2000m
Correction factors:
2 000 m < A ≤ 3 000m 3 000 m < A ≤ 4 000m
UE 0.95 0.80
Ie 0.85 0.85
Storage
1 year maximum
Maximum storage temperature: +55 °C
80 % humidity without condensation at 55°C
ø 1 mm
IP rating
IP41 in the SOCOMEC polycarbonate modular enclosure see page page 18
IP2x for non-enclosed modular product
Protection class: Class 1

Other manuals for socomec ATyS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the socomec ATyS Series and is the answer not in the manual?

socomec ATyS Series Specifications

General IconGeneral
TypeAutomatic Transfer Switch (ATS)
Transfer ModeOpen or closed transition
ControlAutomatic, Manual, Remote
StandardsIEC 60947-6-1
CommunicationModbus, Ethernet
Protection DegreeIP20
Poles3 or 4 poles