ATyStM - 542931D - SOCOMEC
26 EN
13.4. Programming
Whilst in manual mode check the wiring and installation. If ok power up the product.
This product must always be put into service by qualied and approved personal.
The LED signalling is only active when the product supply is on (supply LED lit).
To set the dip switches, it is necessary to open the AUTO/MANU cover.
The commissioning must always result in having at least 1 LED source available lit..
Therefore, the voltage and frequency must be within the dened thresholds.
Any action on the potentiometers changes the settings, even if the cover is closed.
13.4.1. Auto-conguration
Once the product is connected, you can congure automatically its nominal voltage & nominal frequency.
Therefore, while front cover is open:
1. Put dip switch A-B in position B.
2. All leds are blinking.
3. All leds are on, not blinking anymore.
4. Put dip switch A-B in position A: product is ready to work.
The LED signalling and operation is only active when the product supply is available.
To set the dip switches, it is necessary to open the Auto/Manual cover.
13.4.2. Sealable conguration cover
Conguration settings may be protected by means of a sealable cover.
Refer to section «5. Optional accessories», page 11.

Other manuals for socomec ATyS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the socomec ATyS Series and is the answer not in the manual?

socomec ATyS Series Specifications

General IconGeneral
TypeAutomatic Transfer Switch (ATS)
Transfer ModeOpen or closed transition
ControlAutomatic, Manual, Remote
StandardsIEC 60947-6-1
CommunicationModbus, Ethernet
Protection DegreeIP20
Poles3 or 4 poles

Related product manuals