EasyManuals Logo

socomec ATyS Series Installation And Operating Manual

socomec ATyS Series
30 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #7 background imageLoading...
Page #7 background image
ATyStM - 542931D - SOCOMEC
7EN
2.2.1. Selection guide
Six ratings 40 / 63 / 80 / 100 / 125 / 160 A
ATyS d M ATyS t M ATyS g M ATyS p M
APPLICATIONS
Normal / Backup without automatic controller
Normal / Backup with built-in automatic controller
Stable positions
Load changeover
FUNCTIONS
POWER SUPPLY
External
Integrated
OPERATION
Backup manual operation of the 3 positions
Electrical (dry contact) control of positions I, 0 and II
•*
Automatic control of positions I, 0 and II
Return to 0 position feature upon loss of source
MONITORING
3 voltages on networks I and II
Frequency on networks I and II
Phase rotation on networks I and II
Asymmetry of networks I and II
AUTOMATIC CONTROLLER CONFIGURATION
By potentiometer and micro-switch
By screen + keyboard
V
n
, F
n
, V threshold, F threshold
Driving with or without priority
Adjustable operating timers
Preset configuration
Control type (impulse or switch / contactor)
DISPLAY
Position, fully visualised breaking
LED: source status, automatic mode, fault LED
LED: switch positions, supply, tests, control
V, F, timers, number of operations, last event
REMOTE CONTROL
Outputs
Generator start / stop order
Product availability (not fault and not manual mode)
•*
Source available
•*
Programmable output (source, availability, fault)
•*
Inputs
Test on load
•*
Retransfer
•*
Automatic mode inhibit
•*
Position O order
•*
Priority
Other programmable inputs
(test off-load, position control, etc.)
•*
Remote control
Human / Machine Interface (D10 and D20)
RS485 communication (MODBUS)
•**
* 3 inputs / 3 outputs (programmable).
** Product reference is different: communication by RS485 connection (MODBUS) allows up to 31 ATyS M to be connected to a PC or a PLC over 1500 m.

Other manuals for socomec ATyS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the socomec ATyS Series and is the answer not in the manual?

socomec ATyS Series Specifications

General IconGeneral
TypeAutomatic Transfer Switch (ATS)
Transfer ModeOpen or closed transition
ControlAutomatic, Manual, Remote
StandardsIEC 60947-6-1
CommunicationModbus, Ethernet
Protection DegreeIP20
Poles3 or 4 poles