HYD 5/6/8/10/15/20KTL-3PH USER MANUAL
33
ATTENTION
On-grid operation
After connecting the external terminals of the inverter,
the recommended power-up sequence is: first turn on
the battery, then turn on DC, then connect to the grid,
and finally connect the load.
After connecting the external terminals of the inverter,
the recommended de-energizing sequence is: first
disconnect the load, then disconnect DC, then
disconnect the battery, and finally disconnect the grid.
NOTE
The open-circuit voltage of the modules connected in
series must be lower than or equal to 1000 V.
The connected PV modules must be compliant with IEC 61730
class
Table. 5-1 Relevant current parameters of each model
Model
Isc PV (absolute
maximum)
Maximum output
overvoltage
protection
HYD 5KTL-3PH
15 A/15 A
8 A*3
HYD 6KTL-3PH
10 A*3
HYD 8KTL-3PH
13 A*3
HYD 10KTL-3PH
30 A/30 A
16 A*3
HYD 15KTL-3PH
24 A*3
HYD 20KTL-3PH
32 A*3
The DVC (decisive voltage classification) is the circuit voltage
which constantly occurs between two arbitrary live parts during
proper use in a worst-case scenario:
Table. 5-2 Description of limits for DVC
DVC
Operating voltage limit(V)
Ac voltage(RMS)
Ac voltage(PK)
Dc voltage(AVG)