HYD 5/6/8/10/15/20KTL-3PH USER MANUAL
88
(A)
for the battery
Discharge Depth (%)
Max. allowed discharge depth
(DOD) for the battery. DOD of
80% means, a battery with 10
kWh capacity can be discharged
to a minimum energy level of 2
kWh.
Discharge Depth
Max. Depth of Discharge (DOD)
for grid-connected mode.
Standard 80%.
When setting the BTS-5K battery
discharge depth, the maximum
limit is 90% to prevent the
battery from being too low to
recharge.
EPS Discharge Depth
Depth of Discharge (DOD) for
EPS mode. Standard: 80%
EPS Safety Buffer
State of charge (SOC), where the
battery will be recharged in EPS
mode. Standard: 20%
Set Force Charge Time
Define the time for the forced
charge. Forced charging takes
place when the SOC of the
battery falls below 8%.
1.2 Auto Configure
Address
Select "Auto configure address",
you can see "Battery quantity"
after entering, and you can
configure the quantity by
yourself
2. Battery Active
Auto Active Control
Enable / disable.
If Automatic activation is
enabled, the inverter will activate
the battery when the inverter
need to discharge or charge the
battery according to the
operational mode settings.
If automatic activation is
disabled, the battery has to be
activated manually by selection