HYD 5/6/8/10/15/20KTL-3PH USER MANUAL
supplied three-phase smart
meter and with this option set to
"enable", the per phase output
current of the inverter will
respond independently.
Important: for this function to
operate properly, the phase on
the smart meter must correlate
to the corresponding phase
when it is wired into the inverter.
1. After setting the EPS mode
enable in standby mode, the
unbalanced support function
will automatically start.
2. After the facility EPS mode is
enabled in the grid connection
state, the unbalanced support
function will automatically start
after the standby mode
12. PV priority charging*
Up to 200 W of PV power is used
for battery charging, the rest in
the normal priority: load, battery
charging, grid feed-in.
Activates RCD type B monitoring
in EPS mode (300 mA)
14. NeutralPointGrounding
When using off-grid mode,
ensure that neutral ground is
enabled. For Australia, South
Africa, and New Zealand, neutral
ground is turned off by default,
refer to 5.3 System Overview
can start and stop a generator
In EPS mode, the dry contact
interface will output a 12V signal
In grid-tied mode, the dry
contact interface will output a
12V signal