JEA USER MANUAL
32 I +44 (1753) 214 500
9. PARAMETERS
9.1 PROBES SELECTION
PARAMETER DESCRIPTION UNITS MIN MAX DEFAULT
tPS Temperature Control Probe (Air) Number N/A, 1 4 1
dPS Defrost Control Probe Number N/A, 1 4 2
cPS Condenser Control Probe Number N/A, 1 4 3
aPS Ambient Control Probe Number N/A, 1 4 4
PPS PIR Sensor Probe Number N/A, 1 4 N/A
HPS Humidity Sensor Probe Number N/A, 1 4 N/A
rHt Relative Humidity Threshold % 10 100 80
Note: If changes are made to the probe connection port, then the probe connected to the JEA must match accordingly and not
as per the connection diagram (connection diagram as per default settings)
Temperature Control Probe (Air)
Selects the Air temperature probe connection port:
N/A = Not connected
1 = Probe 1
2 = Probe 2
3 = Probe 3
4 = Probe 4
Defrost Control Probe (Evaporator)
Selects the defrost temperature probe connection port:
N/A = Not connected
1 = Probe 1
2 = Probe 2
3 = Probe 3
4 = Probe 4
Condenser Control Probe
Selects the condenser temperature probe connection port:
N/A = Not connected
1 = Probe 1
2 = Probe 2
3 = Probe 3
4 = Probe 4
Ambient Control Probe
Selects the ambient temperature probe connection port:
N/A = Not connected
1 = Probe 1
2 = Probe 2
3 = Probe 3
4 = Probe 4
PIR Sensor Probe
Selects the PIR sensor connection port:
N/A = Not connected
1 = Probe 1
2 = Probe 2
3 = Probe 3
4 = Probe 4