Humidity Sensor Probe
Selects the humidity sensor connection port:
N/A = Not connected
1 = Probe 1
2 = Probe 2
3 = Probe 3
4 = Probe 4
Relative Humidity Threshold
The threshold above which high humidity mode is entered. In high humidity mode, the evaporator fan is always
ON, overriding other fan settings.
Note: Temperature probe selection has priority so PIR and humidity sensor should not use any of the inputs already congured
for probes.
9.2 TEMPERATURE REGULATION
PARAMETER DESCRIPTION UNITS MIN MAX DEFAULT
dnO
Normal Mode Cut-Out – DAY °C
°F
-40
-40
40
104°F
1
33.8
dnI Normal Mode Cut-In – DAY
°C
°F
-40
-40
40
104
4
39.2
dEO ECO Mode Cut-Out – DAY
°C
°F
-40
-40
40
104
5
41
dEI ECO Mode Cut-In – DAY
°C
°F
-40
-40
40
104
8
46.4
dSO SUPERFROST Mode Cut-Out – DAY
°C
°F
-40
-40
40
104
-3
26.6
dSI SUPERFROST Mode Cut-In – DAY
°C
°F
-40
-40
40
104
0
32
nnO Normal Mode Cut-Out – NIGHT
°C
°F
-40
-40
40
104
3
37.4
nnI Normal Mode Cut-In – NIGHT
°C
°F
-40
-40
40
104
6
42.8
nEO ECO Mode Cut-Out – NIGHT
°C
°F
-40
-40
40
104
7
44.6
nEI ECO Mode Cut-In – NIGHT
°C
°F
-40
-40
40
104
10
50
nSO SUPERFROST Mode Cut-Out – NIGHT
°C
°F
-40
-40
40
104
0
32
nSI SUPERFROST Mode Cut-In – NIGHT
°C
°F
-40
-40
40
104
3
37.4
tbt Temperature Blind Time Seconds 0 255 10
tdu Temperature Display Unit °F - Fahrenheit / °C - Celsius °C
Normal Mode Cut-Out – DAY
The temperature at which the compressor will turn OFF when the system is running in Day-Normal mode. The
compressor will remain ON until the temperature reaches the Cut-Out temperature.
Normal Mode Cut-In – DAY
The temperature at which the compressor will turn ON when the system is running in Day-Normal mode. If the
temperature is below this value, the compressor will remain OFF
ECO Mode Cut-Out – DAY
The temperature at which the compressor will turn OFF when the system is running in Day-Eco mode. The
compressor will remain ON until the temperature reaches the Cut-Out temperature.