JEA USER MANUAL
sollateksupport@sollatek.com I 33
A3+ CMYK
Humidity Sensor Probe
Selects the humidity sensor connection port:
N/A = Not connected
1 = Probe 1
2 = Probe 2
3 = Probe 3
4 = Probe 4
Relative Humidity Threshold
The threshold above which high humidity mode is entered. In high humidity mode, the evaporator fan is always
ON, overriding other fan settings.
Note: Temperature probe selection has priority so PIR and humidity sensor should not use any of the inputs already congured
for probes.
9.2 TEMPERATURE REGULATION
PARAMETER DESCRIPTION UNITS MIN MAX DEFAULT
dnO
Normal Mode Cut-Out – DAY °C
°F
-40
-40
40
104°F
1
33.8
dnI Normal Mode Cut-In – DAY
°C
°F
-40
-40
40
104
4
39.2
dEO ECO Mode Cut-Out – DAY
°C
°F
-40
-40
40
104
5
41
dEI ECO Mode Cut-In – DAY
°C
°F
-40
-40
40
104
8
46.4
dSO SUPERFROST Mode Cut-Out – DAY
°C
°F
-40
-40
40
104
-3
26.6
dSI SUPERFROST Mode Cut-In – DAY
°C
°F
-40
-40
40
104
0
32
nnO Normal Mode Cut-Out – NIGHT
°C
°F
-40
-40
40
104
3
37.4
nnI Normal Mode Cut-In – NIGHT
°C
°F
-40
-40
40
104
6
42.8
nEO ECO Mode Cut-Out – NIGHT
°C
°F
-40
-40
40
104
7
44.6
nEI ECO Mode Cut-In – NIGHT
°C
°F
-40
-40
40
104
10
50
nSO SUPERFROST Mode Cut-Out – NIGHT
°C
°F
-40
-40
40
104
0
32
nSI SUPERFROST Mode Cut-In – NIGHT
°C
°F
-40
-40
40
104
3
37.4
tbt Temperature Blind Time Seconds 0 255 10
tdu Temperature Display Unit °F - Fahrenheit / °C - Celsius °C
Normal Mode Cut-Out – DAY
The temperature at which the compressor will turn OFF when the system is running in Day-Normal mode. The
compressor will remain ON until the temperature reaches the Cut-Out temperature.
Normal Mode Cut-In – DAY
The temperature at which the compressor will turn ON when the system is running in Day-Normal mode. If the
temperature is below this value, the compressor will remain OFF
ECO Mode Cut-Out – DAY
The temperature at which the compressor will turn OFF when the system is running in Day-Eco mode. The
compressor will remain ON until the temperature reaches the Cut-Out temperature.