JEA USER MANUAL
sollateksupport@sollatek.com I 43
A3+ CMYK
HAd Heater Activation Delay Minutes 0 255 0
HdF Heater Activation Temperature Differential °C
°F
0
0
25
45
2
4
Enable Winter Mode
Select whether Winter mode is enabled
No = Winter mode disable. Other Winter mode parameters ignored
Yes = Winter mode enabled
Heater Activation Temperature Threshold
The minimum regulation temperature which will trigger the JEA to enter Winter mode if lower for longer than the
Heater Activation Delay.
Heater Activation Delay
The maximum permitted time that the Heater Activation Temperature Threshold can be exceeded before
triggering Winter Mode.
Heater Activation Temperature Differential
The temperature differential above the Heater Activation Temperature Threshold, which will turn OFF the heater
and normal operation mode is resumed.
Note: If Winter mode is enabled and activated, then defrost function will be disabled until the Winter mode is terminated.
Note: If the JEA is in Winter mode and the Regulation Probe is detected to be faulty, then the JEA will exit Winter mode and
will resume normal operating mode.
9.13 AMBIENT CONDITION INTERACTION
PARAMETER DESCRIPTION UNITS MIN MAX DEFAULT
AnA Enable Ambient Temperature Interaction - No / Yes Yes
AdE Enable Defrost In High Ambient Condition - No / Yes Yes
An Nominal Ambient Condition
°C
°F
0
32
90
194
40
104
An1 Ambient Change Threshold 1
°C
°F
0
0
10
18
5
9
An2 Ambient Change Threshold 2
°C
°F
0
0
10
18
10
18
AS1 Regulation Temperature Limit Change On An1
°C
°F
-5
-9
5
9
0
0
AS2 Regulation Temperature Limit Change On An2
°C
°F
-5
-9
5
9
0
0
ALL Lower Ambient Safety Limit
°C
°F
-50
-58
0
32
-40
-40
ALU Upper Ambient Safety Limit
°C
°F
0
32
80
176
40
104
Note: This functionality is adjusting the Set Point (cut-in and cut-out values in any operating mode) to reduce energy
consumption according to ambient conditions.
Enable Ambient Temperature Interaction
Select whether the cut-in and cut-out values (set point) are inuenced by the ambient temperature
No = Ambient temperature will be ignored and no adjustments will be made to the compressor cut-in and cut-
out values
Yes = Adjustments will be made based on the ambient temperature
Enable Defrost in High Ambient Condition
Select whether defrost occurs when the ambient temperature rises above nominal ambient conditions (An).
Enable Ambient Temperature Interaction (AnA) must be enabled, and the ambient temperature probe is