11.7 CONDENSER OVER TEMPERATURE
• Compressor: OFF
• Evaporate Fan: ON (respecting the door switch status)
With Display
• Master Alarm Indicator: ON
• Main Display: Toggles between the regulation probe temperature and COt
Without Display
• Green Power Icon: ON
• Yellow Compressor Icon: OFF
• Red Alarm Icon: Flashing twice (500 ms ON / 500 ms) every 10 seconds
Note: If three consecutive OH events occur, then the JEA will Initiate Refrigeration Failure Mode
11.8 CONDENSER UNDER TEMPERATURE
• Compressor: OFF
• Evaporate Fan: ON (respecting the door switch status)
With Display
• Master Alarm Indicator: ON
• Main Display: Toggles between the regulation probe temperature and CUt
Without Display
• Green Power Icon: ON
• Yellow Compressor Icon: OFF
• Red Alarm Icon: Flashing twice (500 ms ON / 500 ms OFF) every 10 seconds
Note: If three consecutive SC events occur, then the JEA will Initiate Refrigeration Failure Mode
11.9 AMBIENT OVER TEMPERATURE
• Compressor: OFF
• Evaporate Fan: ON or Cycling (respecting the Evaporator Fan Management settings)
With Display
• Master Alarm Indicator: ON
• Main Display: Toggles between the regulation probe temperature and AOt
Without Display
• Green Power Icon: ON
• Yellow Compressor Icon: OFF
• Red Alarm Icon: Flashing (2 s ON / 500 ms OFF)
• Defrost is disabled
11.10 AMBIENT UNDER TEMPERATURE
• Compressor: OFF
• Evaporate Fan: ON or Cycling (respecting the Evaporator Fan Management settings)
With Display
• Master Alarm Indicator: ON
• Main Display: Toggles between the regulation probe temperature and AOt
Without Display
• Green Power Icon: ON
• Yellow Compressor Icon: OFF
• Red Alarm Icon: Flashing (2 s ON / 500 ms OFF)
• Defrost is disabled