JEA USER MANUAL
sollateksupport@sollatek.com I 37
A3+ CMYK
9.4 VOLTAGE PROTECTION CONTROL
PARAMETER DESCRIPTION UNITS MIN MAX DEFAULT
UPt Enable Voltage Protection Feature - No / Yes Yes
UHo High Voltage Disconnect V AC 60 300 266
UHi High Voltage Reconnect V AC 60 300 260
ULo Low Voltage Disconnect V AC 60 300 180
ULI Low Voltage Reconnect V AC 60 300 186
Hbt High Voltage Blind Time Seconds 0 25 0.5
Lbt Low Voltage Blind Time Seconds 0 25 2
Enable Voltage Protection Feature
Select whether voltage protection is active
No = Voltage protection is disabled. All other voltage protection parameters become de-active, and JEA will not
respond to High or Low Voltage
Yes = Voltage Protection is enabled. JEA will act according to set parameters
High Voltage Disconnect
The maximum allowable voltage before the JEA disconnects power to all the outputs
High Voltage Reconnect
The voltage, which the JEA will reconnect power to all the outputs after a High Voltage Disconnect event.
Low Voltage Disconnect
The minimum allowable voltage before the JEA disconnects power to all the outputs
Low Voltage Reconnect
The voltage, which the JEA will reconnect power to all the outputs after a Low Voltage Disconnect event.
High Voltage Blind Time
The duration of the voltage must be higher/lower than the High Voltage Disconnect (UHo)/High Voltage
Reconnect (UHi) before disconnecting/reconnecting power to the compressor and outputs.
Low Voltage Blind Time
The duration of the voltage must be lower/higher than the Low Voltage Disconnect (ULo)/Low Voltage Reconnect
(ULi) before disconnecting/reconnecting power to the compressor and outputs.
9.5 DELAYS & TIMERS
PARAMETER DESCRIPTION UNITS MIN MAX DEFAULT
Itd Intelligent Time Delay Seconds 0 300 180
Cd0 First Plug-In Delay Seconds 0 255 10
Cd3 Minimum Compressor Off Time Minutes 0 255 3
Cd4 Minimum Compressor On Time Minutes 0 255 1
LAd Loads Activation Delay Seconds 0 255 3
Cd5 Maximum Compressor On Time Forced Defrost Hours N/A, 1 50 4
Cd6 Maximum Compressor On Time Refrigeration Fault Hours N/A, 1 50 6
dCO Compressor On Cycle Probe#1 Faulty - Day Minutes 0 255 2
dCF Compressor Off Cycle Probe#1 Faulty - Day Minutes 0 255 3