7 Teleservice Application Framework
User Manual 215/374
7.3.6.3 Static mode
7.3.6.3.1 Basic DLC file structure
Every datalogger configuration file has the following basic components:
Necessary DLC file objects
Parameter
Description
[JOBOPTIONS]
Start tag of the DLC file
ACTIVE
Active flag will be automatically set to 1 by ylogd after correct file parsing
LFJNAME
Name of the log file job
LFFORMAT
Format of the data logger file:
1 : ASCII_STD
2 : ASCII_TC1
3 : ASCII_CSV
4 : BINARY_C2C_LE
5 : BINARY_TC3_LE
MEMSIZE
Maximum size of the data logger file in bytes (Maximum value is 500 MB)
BASIC_SAMPLE_TIME
Time interval in which is checked whether the values have changed
TIMESTAMP
Time stamp at the beginning of every new logged line in the data logger
file
[FILEHEADER]
Start tag of the log-file
COMMENT
Comment
[SAMPLECONDITIONS]
Start tag of the values which shall be logged chapter
NUMCONDITIONS
Number of values which shall be logged
[MASTERSAVECONDITIONS]
Start of the chapter for master save conditions.
See also How the logger mechanism works (see "Introduction" on page
189).
NUMMASTERSAVECONDITIONS
Number of master save conditions which must be valid before the
"normal" save conditions are checked
[SAVECONDITIONS]
Start of the chapter for save conditions.
See also How the logger mechanism works (see "Introduction" on page
189)
LOG_MECHANISM
Log mechanism modes: