Fault Code Fault Name Corrective Measures
548-563, 580-
595
PV Abnormal
Alarm
Check whether the voltage and current of the in-
verter is abnormal to determine the cause of the
alarm.
1. Check whether the corresponding module is
sheltered. If so, remove the shelter and ensure
module cleanness.
2. Check whether the battery board wiring is
loose, if so, make it reliably connected.
3. Check if the DC fuse is damaged. If so, replace
the fuse.
4. Contact Sungrow Customer Service if the pre-
ceding causes are ruled out and the alarm
persists.
*The code 548 to code 563 are corresponding to
string 1 to string 16 respectively.
*The code 580 to code 595 are corresponding to
string 17 to string 32 respectively.
37
Excessively High
Ambient
Temperature
Generally, the inverter will resume operation
when the internal or module temperature returns
to normal. If the fault persists:
1. Check whether the ambient temperature of the
inverter is too high;
2. Check whether the inverter is in a well-venti-
lated place;
3. Check whether the inverter is exposed to di-
rect sunlight. Shield it if so;
4. Check whether the fan is running properly. Re-
place the fan if not;
5. Contact Sungrow Power Customer Service if
the fault is due to other causes and the fault
persists.
43
Excessively Low
Ambient
Temperature
Stop and disconnect the inverter. Restart the in-
verter when the ambient temperature rises within
the operation temperature range.
9 Troubleshooting and Maintenance User Manual

Table of Contents

Other manuals for Sungrow SG50CX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sungrow SG50CX and is the answer not in the manual?

Sungrow SG50CX Specifications

General IconGeneral
Max. DC Voltage1100 V
MPPT Voltage Range200 V - 1000 V
Max. Input Current per MPPT26 A
Number of MPPTs4
Rated AC Output Power50 kW
Max. AC Output Current76 A
Frequency50 Hz / 60 Hz
Efficiency98.6%
Start Voltage200 V
Number of DC Inputs per MPPT2
Max. AC Apparent Power55 kVA
AC Voltage Range310 V - 480 V
Power Factor at Rated Power1
Adjustable Power Factor Range0.8 leading - 0.8 lagging
THDi< 3%
DC SwitchYes
AC Surge ProtectionType II
DC Surge ProtectionType II
Protection ClassI
Cooling MethodSmart forced air cooling
Protection DegreeIP66
Protection LevelIP66
Operating Temperature Range-25°C to +60°C
Humidity0-100%
AC Output Voltage3 / N / PE, 220 V / 380 V, 230 V / 400 V