97
Fault Code Fault Name Corrective Measures
39
Low System Insu-
lation Resistance
Wait for the inverter to return to normal. If the
fault occurs repeatedly:
1. Check whether the ISO resistance protection
value is excessively high via the app or the LCD,
and ensure that it complies with the local
regulations.
2. Check the resistance to ground of the string
and DC cable. Take corrective measures in case
of short circuit or damaged insulation layer.
3. If the cable is normal and the fault occurs on
rainy days, check it again when the weather turns
fine.
4. If there are batteries, check whether battery
cables are damaged and whether terminals are
loose or in poor contact. If so, replace the dam-
aged cable and secure terminals to ensure a reli-
able connection.
5. Contact Sungrow Customer Service if the pre-
ceding causes are ruled out and the fault persists.
106
Grounding Cable
Fault
1. Check whether the AC cable is correctly
connected.
2. Check whether the insulation between the
ground cable and the live wire is normal.
3. Contact Sungrow Customer Service if the pre-
ceding causes are ruled out and the fault persists.
88 Electric Arc Fault
1. Disconnect the DC power supply, and check
whether any DC cable is damaged, the connec-
tion terminal or fuse is loose or there is a weak
contact. If so, replace the damaged cable, fasten
the terminal or fuse, and replace the burnt
component.
2. After performing step 1, reconnect the DC
power supply, and clear the electric arc fault via
the App or the LCD, after that the inverter will re-
turn to normal.
3. Contact Sungrow Customer Service if the fault
persists.
User Manual 9 Troubleshooting and Maintenance

Table of Contents

Other manuals for Sungrow SG50CX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sungrow SG50CX and is the answer not in the manual?

Sungrow SG50CX Specifications

General IconGeneral
Max. DC Voltage1100 V
MPPT Voltage Range200 V - 1000 V
Max. Input Current per MPPT26 A
Number of MPPTs4
Rated AC Output Power50 kW
Max. AC Output Current76 A
Frequency50 Hz / 60 Hz
Efficiency98.6%
Start Voltage200 V
Number of DC Inputs per MPPT2
Max. AC Apparent Power55 kVA
AC Voltage Range310 V - 480 V
Power Factor at Rated Power1
Adjustable Power Factor Range0.8 leading - 0.8 lagging
THDi< 3%
DC SwitchYes
AC Surge ProtectionType II
DC Surge ProtectionType II
Protection ClassI
Cooling MethodSmart forced air cooling
Protection DegreeIP66
Protection LevelIP66
Operating Temperature Range-25°C to +60°C
Humidity0-100%
AC Output Voltage3 / N / PE, 220 V / 380 V, 230 V / 400 V

Related product manuals