98
Fault Code Fault Name Corrective Measures
84
Reverse Connec-
tion Alarm of the
Meter/CT
1. Check if the meter is wrongly connected.
2. Check if the input and output wiring of the me-
ter is reversed.
3. If the existing system is enabled, please check
if the rated power setting of the existing inverter
is correct.
514
Meter Communi-
cation Abnormal
Alarm
1. Check whether the communication cable and
the terminals are abnormal. If so, correct them to
ensure reliable connection.
2. Reconnect the communication cable of the
meter.
3. Contact Sungrow Customer Service if the pre-
ceding causes are ruled out and the alarm
persists.
323 Grid Confrontation
1. Check whether the output port is connected to
actual grid. Disconnect it from the grid if so.
2. Contact Sungrow Customer Service if the pre-
ceding causes are ruled out and the fault persists.
75
Inverter Parallel
Communication
Alarm
1. Check whether the communication cable and
the terminals are abnormal. If so, correct them to
ensure reliable connection.
2. Reconnect the communication cable of the
meter.
3. Contact Sungrow Customer Service if the pre-
ceding causes are ruled out and the alarm
persists.
9 Troubleshooting and Maintenance User Manual

Table of Contents

Other manuals for Sungrow SG50CX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sungrow SG50CX and is the answer not in the manual?

Sungrow SG50CX Specifications

General IconGeneral
Max. DC Voltage1100 V
MPPT Voltage Range200 V - 1000 V
Max. Input Current per MPPT26 A
Number of MPPTs4
Rated AC Output Power50 kW
Max. AC Output Current76 A
Frequency50 Hz / 60 Hz
Efficiency98.6%
Start Voltage200 V
Number of DC Inputs per MPPT2
Max. AC Apparent Power55 kVA
AC Voltage Range310 V - 480 V
Power Factor at Rated Power1
Adjustable Power Factor Range0.8 leading - 0.8 lagging
THDi< 3%
DC SwitchYes
AC Surge ProtectionType II
DC Surge ProtectionType II
Protection ClassI
Cooling MethodSmart forced air cooling
Protection DegreeIP66
Protection LevelIP66
Operating Temperature Range-25°C to +60°C
Humidity0-100%
AC Output Voltage3 / N / PE, 220 V / 380 V, 230 V / 400 V